WAC 51-11C-40807

WAC 51-11C-40807. Section C408.7 — Refrigeration system commissioning

Last amended: 2020Year: 2026Length: 121 wordsOfficial source
C408.7 Refrigeration system commissioning. All installed refrigeration systems subject to Section C410 shall be included in the commissioning process required by Section C408.1. EXCEPTIONS: 1. Self-contained refrigeration systems are exempt from the commissioning process. 2.Total installed capacity for refrigeration is equal to or less than 240 kBtu/h. C408.7.1 System testing. Functional performance testing shall demonstrate that compressors, heat exchangers, piping, distribution systems, and system-to-system interfacing relationships are installed and operate in accordance with approved construction documents. Testing shall include the sequence of operation and be conducted under full-load at, part-load and the following conditions: 1. Normal mode; 2. Redundant or automatic back-up mode; 3. Performance of alarms; and 4. Mode of operation upon a loss of power and restoration of power.