WAC 51-11C-61081
WAC 51-11C-61081. Section A108.1 — General
A108.1 General. Tables A108.1(1) and A108.1(2) list effective air change rates and heat capacities for heat loss due to infiltration for Single-Family Residential.
The estimated seasonal average infiltration rate in air changes per hour (ACH) is given for standard air-leakage control (see Section R402.4 for air leakage requirements for Single-Family Residential). The effective air change rate shall be used in calculations for compliance under either the Component Performance or Systems Analysis approaches.
Heat loss due to infiltration shall be computed using the following equation:
Q infil = ACH eff * HCP Where: Q infil = Heat loss due to air infiltration. ACH eff = The effective air infiltration rate in Table A108.1(1) HCP = The Heat Capacity Density Product for the appropriate elevation or climate zone as given below.
Q infil
=
ACH eff * HCP
Where:
Q infil
=
Heat loss due to air infiltration.
ACH eff
=
The effective air infiltration rate in Table A108.1(1)
HCP
=
The Heat Capacity Density Product for the appropriate elevation or climate zone as given below.
Table A108.1(1)
Assumed Effective Air Changes
per Hour
Air-Leakage Air Changes per Hour Control Package Natural Effective Standard 0.35 0.35
Air-Leakage
Air Changes per Hour
Control Package
Natural
Effective
Standard
0.35
0.35
Table A108.1(2)
Default Heat Capacity/Density
Product for Air
Zone Average Elevation Heat Capacity/Density 1 Mean Sea Level 0.0180 Btu/h • °F 2 2000 0.0168 Btu/h • °F 3 3000 0.0162 Btu/h • °F
Zone
Average Elevation
Heat Capacity/Density
1
Mean Sea Level
0.0180 Btu/h • °F
2
2000
0.0168 Btu/h • °F
3
3000
0.0162 Btu/h • °F