WAC 51-11C-90500. Appendix F — Outcome-based energy budget
Informational Note: The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.
F101.1 General. This section is an outcome-based energy budget compliance requirement pursuant to RCW 19.27A.160 to incrementally move toward achieving by 2031 a 70 percent reduction in annual net energy use compared with 2006 baseline. As an outcome-based energy budget, this requirement uses a building's actual energy use to determine compliance.
F101.2 Scope. Buildings permitted under this section shall document one year of net energy use below an energy budget within 3 years after occupancy and every 5 years thereafter. Buildings and sites shall also be designed with the ability to offset in the future all estimated energy needs through renewable energy generation with minimum 40 percent on-site, maximum 40 percent off-site, and maximum 20 percent through green power purchase. Buildings that exceed the energy budget by up to 20 percent shall offset the excess amount through a green power purchase agreement. Buildings that exceed the energy budget by more than 20 percent shall, using a posted performance bond or financial security, offset the excess amount over 20 percent by installing renewable energy or with an energy retrofit.
F101.3 Building permit submittal. Building designs shall establish on the Washington State Outcome-Based Energy Budget form (Figure F101.3):
1. The anticipated building energy use is lower than the energy budget.
2. The energy generation ability in the future is greater than or equal to the anticipated building energy use.
F101.3.1 Anticipated building energy use. The total yearly energy use from all metered fuel sources is the anticipated building energy use. Any energy used from district energy, combined heat and power, renewable energy, or captured waste heat systems must be metered. Buildings with any nonmetered energy sources are not permitted for compliance with this section. All secondary spaces and services (examples: Exterior building and site lighting, surface parking, garages, and exterior swimming pools) associated with the building shall be included in the overall energy use total. The anticipated site Energy Use Intensity (EUI) for each fuel source shall be reported in units of kWh/ft 2 /yr or kBtu/ft 2 /yr using the conversions listed below:
Metered Fuel Source to kWh: to kBTU: Electric kWh × 1 kWh × 3.412 Gas Therm × 29.308 Therm × 100 Propane Cubic Foot × 0.738 Cubic Foot × 2.5185 Fuel Oil Gallon × 43.872 Gallon × 149.6905
Metered Fuel Source
to kWh:
to kBTU:
Electric
kWh × 1
kWh × 3.412
Gas
Therm × 29.308
Therm × 100
Propane
Cubic Foot × 0.738
Cubic Foot × 2.5185
Fuel Oil
Gallon × 43.872
Gallon × 149.6905
F101.3.2 Building use and occupancy types. Building use and occupancy types permitted are indicated in Table F101.3.2(1).
F101.3.3 Maximum site energy budget. Table F101.3.2(1) indicates the site EUI budget for each building use and occupancy type along with the building enclosure requirements for all use and occupancy types.
F101.3.3.1 Mixed-use buildings. For buildings that contain more than one building use or occupancy type, the overall energy budget shall be based on the individual floor area percentage totals of each use times the individual energy budget and summing the results of all individual areas.
F101.3.3.2 Energy budget level options. Development teams may commit to a future, more stringent energy budget level from Table F101.3.2(1). Actual energy use and energy generation ability will be evaluated on this lower budget level.
F101.3.3.3 Energy modeling. A proposed building energy model is required for compliance with Section F101.3.2. A baseline energy model is not required. The proposed design model must show estimated energy use below the energy.
F101.3.4 Energy generation ability. Permit documents shall indicate the location, space allocated, and connection pathways for future installation of all potential energy generation systems. Only items defined by the Washington State Energy Code as on-site renewable energy shall be used to meet energy generation requirements.
F101.3.4.1 Energy generation categories. The development team shall complete the Washington State Outcome-Based Energy Budget form (Figure F101.3) to show the total renewable energy generation ability in the following categories:
1. Building integral: Renewable energy generation sources attached to the building. This value, combined with the on-site value, shall be at least 40 percent of the energy budget.
2. On-site: Renewable energy generation sources located on the building site property. This value, combined with the building integral value, shall be at least 40 percent of the energy budget.
3. Off-site: Renewable energy generation sources not located on the building site. This amount is limited to 40 percent of the energy budget. A specific off-site location does not need to be identified.
4. Green Power: Renewable energy purchased through the electric utility provider for the building. This amount is limited to 20 percent of the energy budget.
F101.3.4.2 Energy generation ability for building sites within a 2030 District. The development team for building sites within a designated 2030 District recognized by Architecture 2030 may use the Architecture 2030 Challenge 70 percent energy reduction target from the 2003 baseline as the energy budget. Building locations meeting this criteria and choosing this energy budget are exempt from the building integral and on-site requirements in Section F101.3.4.1. Green power remains capped at 20 percent. The generation requirements may be split, in any amount, among the building integral, on-site, or off-site categories. Actual energy use will be evaluated against the Architecture 2030 Challenge 70 percent energy reduction budget.
F101.4 Actual energy use submittal. The building owner or representative shall submit energy use documentation summary from all energy source providers or from an energy benchmarking service to the building code official. Code compliance is achieved with net energy use below the energy budget for any continuous 12-month span within the first 3 years of occupancy.
F101.4.1 Energy use monitoring period and occupancy. The energy use monitoring time frame shall start on the first full-month billing cycle of the utility or energy source provider(s) 6 months after a certificate of occupancy is issued. Buildings shall be deemed substantially occupied when a minimum 85 percent of the floor area, including all common areas, is occupied. The energy monitoring start time may be delayed up to an additional 6 months from certificate of occupancy (up to 12 months total) if 85 percent occupancy is not yet achieved. Buildings not 85 percent occupied after 12 months shall start the monitoring period for the portions occupied with an energy budget based on the spaces occupied and all common areas combined.
F101.4.2 Change of occupancy use during monitoring period. If an area within the building changes from one occupancy use to another with a different target EUI energy budget or if the building occupancy level drops below 50 percent, the target EUI energy budget shall be recalculated to become the new energy budget against which the building energy use shall be compared for compliance.
F101.4.3 Energy metering. All building spaces and uses subject to an energy budget or a portion of the energy budget shall be metered separately for all energy uses.
F101.4.4 Energy budget responsibility. The building owner is responsible for the compliance of the whole building. At the building owner's discretion, responsibility for the energy use budget may be divided and transferred into portions attributable to the occupant, operator or controller of each energy budget space. Common area spaces not under the control of an occupant or tenant may not be transferred.
F101.5 Actual energy use above the energy budget. Buildings exceeding the energy budget are not in compliance with the energy code and the building owner shall complete one of the following measures within 1 year:
1. Owners of buildings with actual energy use that exceeds the energy budget by up to 20 percent may offset the excess energy amount through annual green power purchase agreement from the utility provider at a rate of 1.1 times the excess energy amount until future code compliance is demonstrated.
2. Owners of buildings with actual energy use that exceeds the energy budget by more than 20 percent and up to 40 percent shall complete item 1 and either install on-building, on-site, or off-site energy generation equipment or invest in an energy conservation retrofit using the performance bond or financial security for energy amount remaining above 20 percent.
3. Owners of buildings with actual energy use that exceeds the energy budget by more than 40 percent shall complete item 1, item 2, and post a replacement performance bond or financial security equal to the first bond or security amount.
F101.5.1 Continued energy monitoring. Upon completing the necessary compliance measure(s) in Section F101.5 the building owner is provided another 3-year time frame to achieve and document net energy use below the energy budget for any continuous 12-month span. Owners of buildings that remain more than 20 percent above the energy budget shall repeat the measures in Section F101.5, up to 3 times maximum, using the performance bond or financial security to install energy generation equipment or to install an energy retrofit and post a new performance bond equal to the first.
F101.5.2 Tradable certificate for energy savings. As an alternate to the requirements of Section F101.5 a building owner may, when this market-based instrument becomes available, purchase a Tradable Certificate for Energy Savings (TCES) or "white certificates" from a building or entity with energy savings. The building owner shall purchase TCES's equal to 1.1 times the amount that the building's actual energy use exceeds the energy budget.
F101.6 Performance bond or financial security. A building developer must secure and submit to the code official a performance bond or an irrevocable financial security letter of credit from a state of Washington financial institution prior to certificate of occupancy issuance. The bond or security shall have a value equal to $4.00 per square foot of gross conditioned floor area. The bond or security shall be used only to install renewable energy on the building or for investment into energy conservation measures as part of an energy retrofit. The bond or security may also be held for one additional 3-year energy-monitoring period if green power is purchased. Upon demonstrated compliance with the energy budget, the bond or security requirement shall be released.
F101.6.1 Failure to submit energy use data. Building owners that fail to submit energy use data at the end of the 3-year monitoring period shall forfeit the full amount of the performance bond or financial security as payment to the local jurisdiction. Building owners that fail to submit energy use data at the end of each continuing five-year monitoring period shall be fined an amount equal to the original bond or financial security by the local jurisdiction.
F101.7 Continued energy budget certification. After achieving code compliance buildings shall be required every 5 years to document a continuous 12-month span with net energy use that is lower than the required energy budget. Owners of buildings with actual energy use that is at least 2.5 percent below their energy budget (from year permitted baseline, not voluntary year) may sell, when a future market-based instrument becomes available, their unused energy equivalents in the form of a "white certificate" or Tradable Certificate for Energy Savings.
F101.8 Local amendments. Local jurisdictions may amend the current code cycle EUI maximum energy budget by adopting a more stringent future code year value stated in Table F101.3.2(1).
Table F101.3.2(1)
Washington State Outcome-Based Energy Budget
Building Occupancy/Use Site EUI 2021 2024 2027 2030 4c 5b 4c 5b 4c 5b 4c 5b B Office - small 19.48 20.60 16.79 17.74 14.09 14.87 11.40 12.00 Office - medium 22.22 24.47 18.91 20.81 15.61 17.16 12.30 13.50 Office - large 21.94 23.06 18.53 19.48 15.11 15.89 11.70 12.30 B Health out-patient 69.75 70.88 58.90 59.85 48.05 48.83 37.20 37.80 E School - primary 25.40 27.20 22.80 24.30 18.99 21.31 14.70 16.50 School - secondary 24.75 28.13 20.90 23.75 17.05 19.38 13.20 15.00 I-2 Hospital 76.60 72.00 68.70 64.50 56.19 57.10 43.50 49.70 M Grocery 98.90 98.40 88.70 88.20 75.56 78.00 58.50 62.70 M Retail - stand alone 30.00 34.50 26.60 30.40 23.20 26.30 19.80 22.20 Retail - strip mall 29.14 34.76 26.53 31.28 23.91 27.79 21.30 24.30 S-1 Garage - enclosed a 7.00 7.00 5.90 5.90 4.90 4.90 3.90 3.90 Garage - open a 4.20 4.20 3.60 3.60 3.00 3.00 2.30 2.30 S-2 Warehouse (nonref) b 6.49 7.61 5.63 6.58 4.76 5.54 3.90 4.50 R-2 kWh/person/year 3,089 3,212 2,681 2,789 2,256 2,348 1,808 1,886 R-2 Common kWh/sf/yr 15.0 15.8 11.6 12.2 8.5 8.9 5.7 5.9
Building Occupancy/Use
Site EUI
2021
2024
2027
2030
4c
5b
4c
5b
4c
5b
4c
5b
B
Office - small
19.48
20.60
16.79
17.74
14.09
14.87
11.40
12.00
Office - medium
22.22
24.47
18.91
20.81
15.61
17.16
12.30
13.50
Office - large
21.94
23.06
18.53
19.48
15.11
15.89
11.70
12.30
B
Health out-patient
69.75
70.88
58.90
59.85
48.05
48.83
37.20
37.80
E
School - primary
25.40
27.20
22.80
24.30
18.99
21.31
14.70
16.50
School - secondary
24.75
28.13
20.90
23.75
17.05
19.38
13.20
15.00
I-2
Hospital
76.60
72.00
68.70
64.50
56.19
57.10
43.50
49.70
M
Grocery
98.90
98.40
88.70
88.20
75.56
78.00
58.50
62.70
M
Retail - stand alone
30.00
34.50
26.60
30.40
23.20
26.30
19.80
22.20
Retail - strip mall
29.14
34.76
26.53
31.28
23.91
27.79
21.30
24.30
S-1
Garage - enclosed a
7.00
7.00
5.90
5.90
4.90
4.90
3.90
3.90
Garage - open a
4.20
4.20
3.60
3.60
3.00
3.00
2.30
2.30
S-2
Warehouse (nonref) b
6.49
7.61
5.63
6.58
4.76
5.54
3.90
4.50
R-2
kWh/person/year
3,089
3,212
2,681
2,789
2,256
2,348
1,808
1,886
R-2
Common kWh/sf/yr
15.0
15.8
11.6
12.2
8.5
8.9
5.7
5.9
a Lighting power allowance must still comply with Table C405.4.2(2).
b Applicable to heated warehouses only.
Table F101.3.2(2)
COMMERCIAL BUILDING TYPE DESCRIPTIONS
Commercial Building Prototype Descriptions Compared to CBSA Building Types
Commercial Prototypes CBSA Detailed Building Type Included Other Criteria Small Office office- admin, professional, government, financial; call center; city hall; retail banking; sales office; other office Less than 20,000 square feet Medium Office office- admin, professional, government, financial; call center; city hall; retail banking; sales office; other office 20,001 - 100,000 square feet Large Office office- admin, professional, government, financial; call center; city hall; retail banking; sales office; other office Greater than 100,000 square feet Stand-alone Retail auto parts; auto/boat dealer/show room; beauty/barber; car wash; clothing; department store; dry cleaner; electronics/appliances; florist, nursery; hardware; home improvement; laundromat (self-service); pharmacy; post office; rental center; repair shop; studio/gallery; vehicle repair; warehouse club; other specialty merchandise Single stand-alone building Strip Mall auto parts; auto/boat dealer/ show room; beauty/barber; car wash; clothing; department store; dry cleaner; electronics/appliances; florist, nursery; hardware; home improvement; laundromat (self-service); pharmacy; post office; rental center; repair shop; studio/gallery; vehicle repair; warehouse club; other specialty merchandise Part of larger mixed-use building Supermarket grocery Primary School elementary school; middle school; pre-school; other k-12 school Secondary School high school Small Hotel motel; bed & breakfast; boarding/rooming house, apt hotel Large Hotel hotel; hotel - resort Hospital hospital Warehouse (non- refrigerated) ministorage; warehouse, distribution; warehouse, storage; other warehouse Quick Service Restaurant cafeteria; catering service; coffee, doughnut, or bagel shop; fast food restaurant; ice cream or frozen yogurt shop; take-out restaurant; truck stop Full-Service Restaurant bar, pub, lounge; sit down restaurant; other restaurant Outpatient Health care dental office; medical clinic/outpatient medical; medical office; medical urgent care clinic; outpatient rehab; veterinarian office/clinic Mid-rise Apartment Not included in CBSA. Should represent all high rise (up to 4 stories) apartment buildings. Census Data used to estimate number of apartments and square footage. Seattle Benchmarking Data used to estimate high rise to mid- rise split in urban area. High-rise Apartment Not included in CBSA. Should represent all low rise (greater than 4 story) apartment buildings. Census Data used to estimate number of apartments and square footage. Seattle Benchmarking Data used to estimate high rise to mid- rise split in urban area. Residential Care assisted living; in-patient rehab; nursing home; retirement home; other residential care
Commercial Prototypes
CBSA Detailed Building Type Included
Other Criteria
Small Office
office- admin, professional, government, financial; call center; city hall; retail banking; sales office; other office
Less than 20,000 square feet
Medium Office
office- admin, professional, government, financial; call center; city hall; retail banking; sales office; other office
20,001 - 100,000 square feet
Large Office
office- admin, professional, government, financial; call center; city hall; retail banking; sales office; other office
Greater than 100,000 square feet
Stand-alone Retail
auto parts; auto/boat dealer/show room; beauty/barber; car wash; clothing; department store; dry cleaner; electronics/appliances; florist, nursery; hardware; home improvement; laundromat (self-service); pharmacy; post office; rental center; repair shop; studio/gallery; vehicle repair; warehouse club; other specialty merchandise
Single stand-alone building
Strip Mall
auto parts; auto/boat dealer/ show room; beauty/barber; car wash; clothing; department store; dry cleaner; electronics/appliances; florist, nursery; hardware; home improvement; laundromat (self-service); pharmacy; post office; rental center; repair shop; studio/gallery; vehicle repair; warehouse club; other specialty merchandise
Part of larger mixed-use building
Supermarket
grocery
Primary School
elementary school; middle school; pre-school; other k-12 school
Secondary School
high school
Small Hotel
motel; bed & breakfast; boarding/rooming house, apt hotel
Large Hotel
hotel; hotel - resort
Hospital
hospital
Warehouse (non- refrigerated)
ministorage; warehouse, distribution; warehouse, storage; other warehouse
Quick Service Restaurant
cafeteria; catering service; coffee, doughnut, or bagel shop; fast food restaurant; ice cream or frozen yogurt shop; take-out restaurant; truck stop
Full-Service Restaurant
bar, pub, lounge; sit down restaurant; other restaurant
Outpatient Health care
dental office; medical clinic/outpatient medical; medical office; medical urgent care clinic; outpatient rehab; veterinarian office/clinic
Mid-rise Apartment
Not included in CBSA.
Should represent all high rise (up to 4 stories) apartment buildings.
Census Data used to estimate number of apartments and square footage. Seattle Benchmarking Data used to estimate high rise to mid- rise split in urban area.
High-rise Apartment
Not included in CBSA.
Should represent all low rise (greater than 4 story) apartment buildings.
Census Data used to estimate number of apartments and square footage. Seattle Benchmarking Data used to estimate high rise to mid- rise split in urban area.
Residential Care
assisted living; in-patient rehab; nursing home; retirement home; other residential care
FIGURE F101.3.2
Washington State Outcome-based Energy Budget Form
WASHINGTON STATE OUTCOME-BASED ENERGY BUDGET FORM (reserved for graphics) Building occupancy/use Conditioned floor area SF Code maximum site EUI energy budget Predicted EUI Electric Gas Propane Oil Other (source/generation) Generation Potential EUI Building Integral (combined must exceed 40%) On-site Off-site (max 40%) Purchase (max 40%) Percentage better than energy budget Percentage potential EUI above predicted EUI PROJECT SUMMARY Building Name Address City Owner Address City, State, Zip PROJECT CERTIFICATION Name Firm Date (seal)
WASHINGTON STATE OUTCOME-BASED ENERGY BUDGET FORM
(reserved for graphics)
Building occupancy/use
Conditioned floor area SF
Code maximum site EUI energy budget
Predicted EUI
Electric
Gas
Propane
Oil
Other (source/generation)
Generation Potential EUI
Building Integral
(combined must exceed 40%)
On-site
Off-site
(max 40%)
Purchase
(max 40%)
Percentage better than energy budget
Percentage potential EUI above predicted EUI
PROJECT SUMMARY
Building Name
Address
City
Owner
Address
City, State, Zip
PROJECT CERTIFICATION
Name
Firm
Date
(seal)