WAC 51-50-0509
WAC 51-50-0509. Section 509 — Incidental uses
Table 509.1
Incidental Uses
Room or Area Separation and/or Protection Dry type transformers over 112.5 kVA and required to be in a fire resistant room per NEC (NFPA 70) Section 450.21 (B) 1 1 hour or provide automatic sprinkler system
Room or Area
Separation and/or Protection
Dry type transformers over 112.5 kVA and required to be in a fire resistant room per NEC (NFPA 70) Section 450.21 (B) 1
1 hour or provide automatic sprinkler system
1 Dry type transformers rated over 35,000 volts and oil-insulated transformers shall be installed in a transformer vault complying with NFPA 70.
1
Dry type transformers rated over 35,000 volts and oil-insulated transformers shall be installed in a transformer vault complying with NFPA 70.
(Remainder of table unchanged)