WAC 173-219-330
WAC 173-219-330. Performance standards
Reclaimed water performance standards. All Class A and Class B reclaimed water at a minimum must meet the technology-based performance standards listed in Table 1 and Table 2 for the class of reclaimed water generated at the facility. Compliance shall generally be measured at the end of treatment, however, the reclaimed water permit may specify alternative monitoring locations and water quality limits to ensure compliance with performance standards, and any additional use based requirements as listed in Table 3.
Table 1: Minimum Biological Oxidation Performance Standards
Biological Oxidation Parameter 1 Minimum Biological Oxidation Performance Standard Dissolved Oxygen Must be measurably present BOD 5 Monthly Average Weekly Average 30 mg/L 45 mg/L CBOD 5 25mg/L 40 mg/L TSS 30 mg/L 45 mg/L pH Minimum Maximum 6 s.u. 9 s.u. pH (Groundwater recharge) 6.5 s.u. 8.5 s.u.
Biological Oxidation
Parameter 1
Minimum Biological Oxidation Performance Standard
Dissolved Oxygen
Must be measurably present
BOD 5
Monthly Average
Weekly Average
30 mg/L
45 mg/L
CBOD 5
25mg/L
40 mg/L
TSS
30 mg/L
45 mg/L
pH
Minimum
Maximum
6 s.u.
9 s.u.
pH (Groundwater recharge)
6.5 s.u.
8.5 s.u.
1 The parameter must be measured at the end of the unit process or alternative monitoring location as set in a reclaimed water permit.
Table 2: Class A and B Performance Standards
Coagulation/Filtration Parameter 1 Class A Reclaimed Water Class B Reclaimed Water Turbidity 2 Monthly Average Sample Maximum Monthly Average Sample Maximum 2 NTU 5 NTU Not Applicable Not Applicable Membrane Filtration Class A Reclaimed Water Class B Reclaimed Water Turbidity 2 Monthly Average Sample Maximum Monthly Average Sample Maximum 0.2 NTU 0.5 NTU Not Applicable Not Applicable Disinfection Class A Reclaimed Water Class B Reclaimed Water Total Coliform 7-Day Median Sample Maximum 7-Day Median Sample Maximum 2.2 MPN/100 mL or CFU/100 mL 23 MPN/mL or CFU/mL 23 MPN/mL or CFU/mL 240 MPN/mL or CFU/mL Virus Removal See disinfection process standards in WAC 173-219-340 Not Applicable Not Applicable Denitrification 3 Class A Reclaimed Water Class B Reclaimed Water Total Nitrogen Monthly Average Weekly Average Monthly Average Weekly Average 10 mg/L 15 mg/L Not Applicable Not Applicable
Coagulation/Filtration
Parameter 1
Class A Reclaimed Water
Class B Reclaimed Water
Turbidity 2
Monthly Average
Sample Maximum
Monthly Average
Sample Maximum
2 NTU
5 NTU
Not Applicable
Not Applicable
Membrane Filtration
Class A Reclaimed Water
Class B Reclaimed Water
Turbidity 2
Monthly Average
Sample Maximum
Monthly Average
Sample Maximum
0.2 NTU
0.5 NTU
Not Applicable
Not Applicable
Disinfection
Class A Reclaimed Water
Class B Reclaimed Water
Total Coliform
7-Day Median
Sample Maximum
7-Day Median
Sample Maximum
2.2 MPN/100 mL or CFU/100 mL
23 MPN/mL or CFU/mL
23 MPN/mL or CFU/mL
240 MPN/mL or CFU/mL
Virus Removal
See disinfection process
standards in WAC 173-219-340
Not Applicable
Not Applicable
Denitrification 3
Class A Reclaimed Water
Class B Reclaimed Water
Total Nitrogen
Monthly Average
Weekly Average
Monthly Average
Weekly Average
10 mg/L
15 mg/L
Not Applicable
Not Applicable
1 The parameter must be measured at the end of the unit process or alternative monitoring location as set in a reclaimed water permit.
2 Sample maximum for turbidity is the highest value for the day that lasts longer than five minutes.
3 Not applicable for beneficial uses 1-13 listed on Table 3: Use-Based Requirements.