40 C.F.R. Table 3 to Subpart EEEE of Part 60

Requirements for Continuous Emission Monitoring Systems (CEMS)

Last amended: 2025Year: 2026Length: 116 wordsOfficial source

Cite as 40 C.F.R. Table 3 to Subpart EEEE of Part 60 (2026)

As stated in § 60.2940, you must comply with the following: For the following pollutants Use the following span values for your CEMS Use the following performance specifications (P.S.) in Appendix B of this part for your CEMS If needed to meet minimum data requirements, use the following alternate methods in Appendix A of this part to collect data 1. Carbon Monoxide 125 percent of the maximum hourly potential carbon monoxide emissions of the waste combustion unit P.S.4A Method 10. 2. Oxygen 25 percent oxygen P.S.3 Method 3A or 3B of Appendix A to this part, or ASME/ANSI PTC 19.10-1981 (IBR, see § 60.17) in lieu of Method 3B only. [90 FR 27953, June 30, 2025]
Cross-references to the CFR
60.1760.2940