46 C.F.R. § 111.05-29

Dual voltage direct current systems.

Last amended: 2016Year: 2026Length: 50 wordsOfficial source

Cite as 46 C.F.R. § 111.05-29 (2026)

Each dual voltage direct current system must have a suitably sensitive ground detection system which indicates current in the ground connection, has a range of at least 150 percent of neutral current rating and indicates the polarity of the fault. [CGD 94-108, 61 FR 28276, June 4, 1996] Grounded Conductors