46 C.F.R. § 111.05-31

Grounding conductors for systems.

Last amended: 2016Year: 2026Length: 125 wordsSubsections: 2Official source

Cite as 46 C.F.R. § 111.05-31 (2026)

(a) A conductor for grounding a direct-current system must be the larger of: (1) The largest conductor supplying the system; or (2) No. 8 AWG (8.4mm 2 ). (b) A conductor for grounding the neutral of an alternating-current system must meet Table 111.05-31(b). Table 111.05-31( b )—Neutral Grounding Conductor for Alternating-Current System Size of the largest generator cable or equivalent for parallel generators—AWG-MCM (mm 2 ) Size of the system grounding conductor—AWG(mm 2 ) Greater than Less than or equal to 2 (33.6) 8 (8.4) 2 (33.6) 0 (53.5) 6 (13.3) 0 (53.5) 3/0 (85.0) 4 (21.2) 3/0 (85.0) 350 MCM (177) 2 (33.6) 350 MCM (177) 600 MCM (304) 0 (53.5) 600 MCM (304) 1100 MCM (557) 2/0 (67.5) 1100 MCM (557) 3/0 (85.0)