HAR §11-280.1-30
HAR §11-280.1-30. Spill and overfill control
Cite as Haw. Code R. § 11-280.1-30
(a)
Owners and operators must ensure that releases due to
spilling or overfilling do not occur. The owner and
operator must ensure that the volume available in the
tank is greater than the volume of product to be
transferred to the tank before the transfer is made
and that the transfer operation is monitored
constantly to prevent overfilling and spilling.
(b)
The owner and operator must report,
investigate, and clean up any spills and overfills in
accordance with section 11-280.1-53.
[Eff 7/15/18;
]
(Auth:
HRS §§342L-3, 342L-32) (Imp:
HRS §§342L-3,
342L-32)
§11-280.1-31
Operation and maintenance of
corrosion protection.
All owners and operators of
metal UST systems with corrosion protection must
comply with the following requirements to ensure that
releases due to corrosion are prevented until the UST
system is permanently closed or undergoes a change-in
service pursuant to section 11-280.1-71:
(1)
All corrosion protection systems must be
operated and maintained to continuously
provide corrosion protection to the metal
components of that portion of the tank and
piping that routinely contain regulated
substances and are in contact with the
ground.
(2)
All UST systems equipped with cathodic
protection systems must be inspected for
proper operation by a qualified cathodic
protection tester in accordance with the
following requirements:
(A)
Frequency. All cathodic protection
systems must be tested within six
280.1-32
3 5 8 4
comp 1/17/20; comp 7 / 8 / 21; comp MAR 2 1 2025
§11-280.1-32
months of installation and at least
every three years thereafter; and
(B)
Inspection criteria. The criteria that
are used to determine that cathodic
protection is adequate as required by
this section must be in accordance with
a code of practice developed by a
nationally recognized association.
(3)
UST systems with impressed current cathodic
protection systems must also be inspected
every sixty days to ensure the equipment is
operating properly.
(4}
For UST systems using cathodic protection,
records of the operation of the cathodic
protection must be maintained, in accordance
with section 11-280.1-34, to demonstrate
compliance with the performance standards in
this section. These records must provide the
following:
(A)
The results of the last three
inspections required in paragraph (3);
and
(B)
The results of testing from the last
two inspections required in paragraph
(2).
[Eff 7/15/18; comp 1/17/20; comp
7/8/21; comp
MAR212025
J
(Auth:
HRS §§342L-3, 342L-32) (Imp:
HRS
§§342L-3, 342L-32)