HAR §11-280.1-32
HAR §11-280.1-32. Compatibility
Cite as Haw. Code R. § 11-280.1-32
(a)
Owners and
operators must use an UST system made of or lined with
materials that are compatible with the substance
stored in the UST system.
(b)
Owners and operators must notify the
department at least thirty days prior to switching to
a regulated substance containing greater than ten
percent ethanol, greater than twenty percent
biodiesel, or any other regulated substance identified
by the department. In addition, owners and operators
with UST systems storing these regulated substances
280.1-33
3 5 8 4
§11-280.1-32
must meet
( 1)
one of the following:
Demonstrate compatibility of the UST system
(including the tank, piping, containment
sumps, pumping equipment, release detection
equipment, spill equipment, and overfill
equipment). Owners and operators may
demonstrate compatibility of the UST system
by using one of the following options:
(A)
Certification or listing of UST system
equipment or components by a nationally
recognized, independent testing
laboratory for use with the regulated
substance stored; or
(B)
Equipment or component manufacturer
approval. The manufacturer's approval
must be in writing, indicate an
affirmative statement of compatibility,
specify the range of biofuel blends the
equipment or component is compatible
with, and be from the equipment or
component manufacturer; or
(2)
Use another option determined by the
department to be no less protective of human
health and the environment than the options
listed in paragraph (1).
(c)
Owners and operators must maintain records
in accordance with section 11-280.1-34 documenting
compliance with subsection (b) for as long as the UST
system is used to store the regulated substance.
[Eff
7ÏT/zÐ;20'2fmp 1/17/20; am and comp 7/8/21; comp
]
(Auth:
HRS §§342L-3, 342L-32)
(Imp:
HRS §§342L-3, 3421-32)