HAR §11-45-55
HAR §11-45-55. Control of access to high radiation areas
Cite as Haw. Code R. § 11-45-55
(a)
The licensee shall ensure that each entrance or access point to a
high radiation area has one or more of the following features:
(1)
A control device that, upon entry into the area,
causes the level of radiation to be reduced below that
level at which an individual might receive a deep dose
equivalent of 0.1 rem (one millisievert) in one hour
at thirty centimeters from the source of radiation
from any surface that the radiation penetrates; or
(2)
A control device that energizes a conspicuous visible
or audible alarm signal so that the individual
entering the high radiation area and the supervisor of
the activity are made aware of the entry; or
(3)
Entryways that are locked, except during periods when
access to the areas is required, with positive control
over each individual entry.
(b)
In place of the controls required by subsection (a)
for a high radiation area, the licensee may substitute continuous
direct or electronic surveillance that is capable of preventing
unauthorized entry.
(c)
The licensee may apply to the department for approval
of alternative methods for controlling access to high radiation
areas.
(d)
The licensee shall establish the controls required by
subsections (a) and (c) in a way that does not prevent individuals
from leaving a high radiation area.
(e)
The licensee is not required to control each entrance
or access point to a room or other area that is a high radiation
area solely because of the presence of radioactive materials
prepared for transport and packaged and labeled in accordance with
the regulations of the U.S. Department of Transportation provided
that:
(1)
The packages do not remain in the area longer than
three days; and
(2)
The dose rate at one meter from the external surface
of any package does not exceed 0.01 rem (0.1
millisievert) per hour.
§11-45-55
45-62
(f)
The licensee is not required to control entrance or
access to rooms or other areas in hospitals solely because of the
presence of patients containing radioactive material, provided
that there are personnel in attendance who are taking the
necessary precautions to prevent the exposure of individuals to
radiation or radioactive material in excess of the established
limits in this subchapter and to operate within the ALARA
provisions of the licensee's radiation protection program.
(g)
The licensee is not required to control entrance or
access to rooms or other areas containing sources of radiation
capable of producing a high radiation area as described in this
section if the licensee has met all the specific requirements for
access and control specified in other applicable subchapters.
[Eff 11/12/99] (Auth: HRS §§321-10, 321-11, 321-71) (Imp: HRS
§§321-1, 321-11(21), 321-71)