HAR §12-223.1-12
HAR §12-223.1-12. Heating boiler room and operating area
Length: 484 wordsOfficial source
Cite as Haw. Code R. § 12-223.1-12
(a) The following shall apply to the care of heating boiler rooms:
(1) The heating boiler room shall be free from accumulation of rubbish, and materials that obstruct access to the boiler, its setting, or firing equipment;
(2) The storage of flammable material or gasoline-powered equipment in the heating boiler room is prohibited;
(3) The roof over heating boilers designed for indoor installations shall be free from leaks and maintained in good condition;
(4) All exit doors shall open outward; and
(5) It is recommended that the ASME BPVC Section VI, covering the care and operation of heating boilers be used as a guide for proper and safe operating practices.
(b) Foundation, supports, and settings. Each heating boiler, potable water heater, and thermal fluid heater and its associated piping must be safely supported. Design of supports, foundations, and settings shall consider vibration (including seismic where necessary), movement (including thermal expansion and contraction), grounding/bonding to minimize electrolytic corrosion, and loadings (including the weight of the fluid in the system during a pressure test) in
223.1-34
3 5 5 9
§12-223.1-12
accordance with jurisdictional requirements,
manufacturers recommendations, and other industry
standards, as applicable.
(c) Exit. Two means of exit shall be provided for
equipment rooms exceeding 500 square feet of floor area
and containing one or more heating boilers, potable
water heaters, or thermal fluid heaters having a
combined fuel capacity of 1,000,000 Btu per hour or more
(or equivalent electrical heat input). Each elevation
shall be provided with at least two means of exit, each
to be remotely located from the other. A platform at the
top of a single heating boiler is not considered an
elevation.
(d) The following shall apply to ladders and
runways:
(1) All walkways, runways, and platforms shall be
of metal construction or equivalent material;
(2) Provided between or over the top of heating
boilers that are more than eight (8) feet
above the operating floor to afford
accessibility for normal operation,
maintenance, and inspection;
(3) Constructed of safety treads, standard
grating, or similar material and have a
minimum width of thirty (30) inches of bolted,
welded, or riveted construction, and equipped
with handrails forty-two (42) inches high with
an intermediate rail and four (4) inches toe
board; and
(4) Stairways that serve as a means of access to
walkways, runways, or platforms shall not
exceed an angle of forty-five (45) degrees
from the horizontal and be equipped with
handrails forty-two (42) inches high with an
intermediate rail.
(e) Drains. At least one floor drain shall be
installed in the equipment room. Drains receiving
blowdown water should be connected to the sanitary sewer
by way of an acceptable blowdown tank or separator or an
air gap that will allow the blowdown water to cool to at
least 140 degrees Fahrenheit and reduce the pressure to
five (5) psig or less.
(f) Water. The following shall apply to water:
223.1-35