HAR §12-45.4-38
HAR §12-45.4-38. Emergency command center
Length: 201 wordsOfficial source
Cite as Haw. Code R. § 12-45.4-38
Section 11.9.5 is
amended by adding Items 12, 13, and 14 to read as follows:
(12) The room shall be accessible from the exterior of the building.
(13) Control panels in the emergency command center shall be
permanently identified as to its function.
(14) Alarm, supervisory and trouble signals shall be annunciated in
compliance with the fire code in the emergency command
center by means of an audible and visual indicator.
[Eff ] (Auth: HRS §132-3) (Imp: HRS §132-3)
(These requirements were in the adopted state fire code Title 12
amendments to the 1997 edition of the Uniform Fire Code. They
provide more direct room access and increased identification of
control panel indicating devices.)
§12-45.4-39 Roof access for one- and two-family dwellings
and townhouses. Section 11.12.2.2.2 is amended to read as follows:
11.12.2.2.2 Roof access for one- and two-Family Dwellings and
Townhouses for photo-voltaic systems. One- and two-family dwellings
need not comply with this section. [Eff ] (Auth: HRS
§132-3) (Imp: HRS §132-3)
(This amendment is being kept because Honolulu, Hawaii and
Kauai counties don’t currently review plans for PV installations for
one- and two-family dwellings. This also coincides with Fire
Operations strategies regarding structure fires involving one- and
two-family dwellings.)