HAR §12-45.4-46
HAR §12-45.4-46. Fire protection systems advanced notification
Length: 745 wordsOfficial source
Cite as Haw. Code R. § 12-45.4-46
Section 13.1.10 is amended by adding Sections 13.1.10.1, 13.1.10.2, and
13.1.10.3 as follows: 13.1.10.1 The county fire department shall be
given a seventy-two hour notification prior to a scheduled inspection,
testing, maintenance, or retesting of any fire protection system (including
class I, II, and III, and combined systems, automatic fire sprinkler
systems, and other fire extinguishing systems) and fire alarm systems
within their respective jurisdiction in the State.
13.1.10.2 Failure to comply with the requirements of this section
will result in the county fire department deeming it an invalid test. A
retest may be required to be performed at the testing company’s
expense.
13.1.10.3 The certificate of fitness holder shall immediately notify
the county fire department of any system inspection, testing or
maintenance cancellations or changes to the scheduled date and time.
[Eff ] (Auth: HRS §132-16) (Imp: HRS §132-16)
(This was in previous state fire codes. This allows the enforcing
authority time to schedule or reschedule availability to witness
any maintenance test by a COF holder.)
§12-45.4-47 Fire protection systems inspection, testing, and
maintenance labeling. Section 13.2.3 is amended by adding sections
13.2.3.3.1, 13.2.3.3.2, 13.2.3.3.2.1, 13.2.3.3.3, 13.2.3.3.3.1,
13.2.3.3.4, 13.2.3.3.4.1, 13.2.3.3.5, 13.2.3.3.5.1, and 13.2.3.3.5.2 as
follows: 13.2.3.3.1 Inspection Label and Collar. An approved label and
verification collar signifying successful passing of the system shall be
provided when inspecting, testing, or maintaining any class I, II, III, and
combined standpipe fire extinguishing system.
13.2.3.3.2 Five Year Inspection Label
13.2.3.3.2.1 Class I, II, and III, and combined standpipe fire
extinguishing systems passing a five-year inspection (annual inspection
for class II hoses) shall have an approved, weatherproof, inspection label
affixed to the fire department connection. If the system does not have a
fire department connection, labels shall be affixed to hose cabinets
located on the ground floor and the top-most floor.
(1)
The label shall indicate the type of system, month and year
the system was inspected, tested, and maintained; the
certificate of fitness holder’s name and certificate number;
and the company name, address, and contact information.
(2)
The label shall be yellow, at least two and one-fourth inches
in width and three and one-fourth of an inch in length, and
clearly visible without obstructing the operation of the fire
extinguishing system.
(3)
The label shall be constructed of a durable material approved
by the AHJ.
(4)
The label shall be punched with no more than one year and
one month.
13.2.3.3.3 Verification Service Collar.
13.2.3.3.3.1 The verification of service collar shall be a circular,
solid of continuous plastic with at least a three inch diameter hole in the
center and shall slide onto each hose length approximately midway from
the male and female couplings after the physical inspection has been
completed and deemed satisfactory. The verification service collar shall:
(1)
Indicate the month and year the hose was inspected; the
certificate of fitness holder’s name and number; and company
name, address and contact information; and
(2)
Be constructed of other suitable materials when approved by
the AHJ.
13.2.3.3.4 Inoperable system sign
13.2.3.3.4.1 Systems that cannot be utilized for firefighting
operations shall have an inoperable system sign affixed to the fire
department connection.
(1)
The tag shall have a white background with red lettering and
be constructed of wood, metal, or plastic.
(2)
The letters shall be a minimum height of three inches and a
minimum width of one-fourth of an inch stroke.
(3)
If the system does not have a fire department connection,
inoperable system signs shall be affixed to hose cabinets
located on the ground floor and the top-most floor.
(4)
The sign shall remain in place until all repairs have been
made and a satisfactory system test is completed.
13.2.3.3.5 Inspection, Testing, and Maintenance Report.
13.2.3.3.5.1 An inspection, testing, and maintenance report
entitled “Standpipe and Hose Systems” available on the State Fire
Council’s website and at each county fire department’s fire prevention
bureau, or a similar report approved by the AHJ, shall be provided to the
property owner or agent within fourteen days after the inspection,
testing, and maintenance date.
13.2.3.3.5.2 An electronic copy of the unsatisfactory test report
shall be submitted to the AHJ within five working days of the inspection,
testing, and maintenance date. Submittals of satisfactory inspection,
testing, and maintenance report shall be determined by the AHJ.
[Eff ] (Auth: HRS §132-16) (Imp: HRS §132-16)
(This revision standardizes the ITM report form & where it may be
found. These amendments standardize the ITM of fire protection
systems identification and AHJ notification requirements).