HAR §12-45.4-57
HAR §12-45.4-57. Fire protection systems table
Length: 1,111 wordsOfficial source
Cite as Haw. Code R. § 12-45.4-57
Sections
13.3.3.2.1, 13.3.3.2.2, 13.3.3.2.3, 13.3.3.2.4, 13.3.3.2.5, and 13.3.3.2.6
are added to read as follows: 13.3.3.2.1 Table 13.2.3.4.3A entitled “Fire
Protection Systems Reference Dates” dated 7/18/2019 may be used as a
reference for applicable codes and standards in effect when the building
was permitted.
(This is useful information for the licensed COF and the AHJ in
determining testing requirements. The fire code committee
discussed this issue and determined to include the table in the
main body of the document (Table 13.2.3.4.3A) CORRECTED by
moving to appropriate section 10/17/17)
13.3.3.2.2 Pretest. The following requirements apply to all
pretesting procedures:
(1)
An air test shall be conducted on the piping between the fire
department connection and the sprinkler riser.
(2)
The piping shall be filled with twenty-five psi of air and
held for fifteen minutes. No drop in pressure is allowed.
(3)
An air test need not be conducted when the piping is above
ground and less than five feet in length.
(4)
Automatic fire sprinkler system without a fire department
connection does not require an air test.
13.3.3.2.3 Inspection, Testing, and Maintenance Label. It shall be
unlawful to inspect, test, or maintain any automatic fire sprinkler system
without providing an approved label signifying successful testing of the
system.
(1)
An approved inspection, testing, and maintenance label
affixed to the fire department connection and the sprinkler
riser. Automatic fire sprinkler systems that do not have a fire
department connection shall have the label affixed to the
riser.
(2)
The label shall indicate the type of system, month and year
the system was tested; certificate of fitness holder’s name
and number; and company’s name, address and contact
information.
(3)
The label shall be clearly visible and punched with no more
than one year and one month.
13.3.3.2.4 The fire department shall be verbally notified
immediately of any system determined to be out of service. Systems
that cannot be utilized for firefighting operations shall have an inoperable
system sign affixed to the fire department connection. The sign shall
remain in place until all repairs have been made and a satisfactory
inspection, test, and maintenance system test is completed.
13.3.3.2.5 Inspection, Testing, and Maintenance Report. An
inspection, testing, and maintenance report entitled “Automatic Sprinkler
Systems” available on the State Fire Council’s website and at each county
fire department’s fire prevention bureau or a similar report approved by
the AHJ, shall be provided to the property owner or agent within fourteen
days after the test.
13.3.3.2.6 An electronic copy of the unsatisfactory report shall be
submitted to the AHJ within five working days. Submittal of a satisfactory
inspection, testing, and maintenance report will be determined by the
AHJ. [Eff ] (Auth: HRS §132-16) (Imp: HRS §132-16)
(This revision standardizes the ITM report form & where it may be
found. Consistent methods of system identification and reporting
to the AHJ are the objectives.)
§12-45.4-58 Stationary fire pump inspection, testing, and
maintenance. Section 13.4.8 is amended to add sections 13.4.8.1 and
13.4.8.2 as follows: 13.4.8.1 Inspection, Testing, and Maintenance
Label. Satisfactory inspection, testing, and maintenance system’s tests
shall have an approved inspection label affixed to the fire pump
controller. The label shall follow the guidelines found in the water-based
fire extinguishing systems inspection labels, tags, and collars.
13.4.8.2 Inspection, Testing, and Maintenance report. An
inspection, testing, and maintenance report entitled “Fire Pumps”
available on the State Fire Council’s website and at each county fire
department’s fire prevention bureau, or a similar report approved by the
AHJ shall be provided to the property owner or agent within fourteen days
after the test. [Eff ] (Auth: RCH §4-105; ROH §1-9.1;
HRS §132-2) (Imp: HRS §132)
(This revision standardizes the ITM report form & where it may be
found. ITM per NFPA 25 helps ensure that the pump is always
ready for service. Amended Sections 13.4.8.1 and 13.4.8.2
ensures consistent testing identification and reporting.)
§12-45.4-59 Private fire service mains inspection, testing,
and maintenance. Section 13.5.4.2 is amended to read as follows:
13.5.4.2 A private fire service main installed in accordance with this code
or the AHJ’s water department shall be inspected, tested, and maintained
in accordance with NFPA 25 and the AHJ’s water department’s inspection,
testing, and maintenance standards. [Eff ] (Auth: RCH
§4-10; ROH §1-9.1; HRS §132-2) (Imp: HRS §132)
(This revision standardizes the ITM report form & where it
may be found. This amendment adds the water department’s ITM
standards to ensure private hydrants are maintained to same
standards as the public hydrants).
§12-45.4-60 Private service mains inspection, testing, and
maintenance schedule. Sections 13.5.4.3, 13.5.4.4, 13.5.4.5,
13.5.4.6, and 13.5.4.7 are added to read as follows: 13.5.4.3 Testing.
An annual inspection, testing, and maintenance shall be conducted by the
certificate of fitness holder. If, during use, the hydrant does not perform
adequately, it shall be tested and, if needed, restored to its proper
operation by a licensed certificate of fitness holder.
13.5.4.4 Fire hydrants that fail the inspection, test, and
maintenance shall have a readily visible, attached “OUT OF SERVICE”
sign. The sign shall have a yellow background with black letters and be
constructed of wood, metal, or plastic. The letters shall be a minimum
height of three inches and a minimum width of one-fourth of an inch
stroke. The sign shall remain in place until all repairs have been made
and a satisfactory hydrant inspection, test and maintenance is completed.
13.5.4.5 The fire department shall be verbally notified immediately
of any fire hydrant determined to be out of service. Fire hydrants
deemed to be permanently inoperable or unusable shall be replaced.
13.5.4.6 Inspection, test, and maintenance report. An inspection,
testing, and maintenance report entitled “Private Fire Service Mains”
available on the State Fire Council’s website and at each county fire
department’s fire prevention bureau, or a similar report approved by the
AHJ, shall be provided to the property owner or agent within fourteen
days after the test.
13.5.4.7 An electronic copy of the unsatisfactory test report shall
be submitted to the AHJ within five working days of the test. The AHJ
shall determine if the submittal of a satisfactory inspection, test, and
maintenance report will be required. [Eff ] (Auth: RCH
§4-105; ROH §1-9.1; HRS §132-2) (Imp: HRS §132)
(This revision standardizes the ITM report form & where it may be
found. Regardless if there were no contractual provisions to
conduct ITM annually or after each use , the hydrant needs to be
ITM by a COF holder when deficiencies are encountered. NFPA 25
states after each use, but their ITM is not that comprehensive
compared to BWS. A one-year annual ITM ensures the hydrant’s
operational use. This section applies consistent identification,
reporting, and notification to the AHJ and the owner.)