32 Ill. Adm. Code 346.330
Irradiator Pools
Section 346.330 Irradiator Pools
a) For
licenses initially issued after December 1, 2005, irradiator pools shall
either:
1) Have
a water-tight stainless steel liner or a liner metallurgically compatible with
other components in the pool; or
2) Be constructed
so that there is a low likelihood of substantial leakage and have a surface
designed to facilitate decontamination.
In either case, the licensee
shall have a method to safely store the sources during repair of the pool.
b) For
licenses initially issued after December 1, 2005, irradiator pools shall have
no outlets more than 0.5 meter below the normal low water level that could
allow water to drain out of the pool. Pipes that have intakes more than 0.5
meter below the normal low water level and that could act as siphons shall have
siphon breakers to prevent the siphoning of pool water.
c) A means shall be
provided to replenish water losses from the pool.
d) A
visible indicator shall be provided in a clearly visible location to indicate
if the pool water level is below the normal low water level or above the normal
high water level.
e) Irradiator
pools shall be equipped with a purification system designed to be capable of
maintaining the water during normal operation at a conductivity of 20 microsiemens
per centimeter or less and with a clarity so that the sources can be seen
clearly.
f) A
physical barrier, such as a railing or cover, shall be used around or over
radiator pools during normal operation to prevent personnel from accidentally falling
into the pool. The barrier may be removed during maintenance, inspection and
service operations.
g) If
long handled tools or poles are used in irradiator pools, the radiation dose
rate in the handling areas of the tools may not exceed 0.02 millisievert (2
millirems) per hour.