35 Ill. Adm. Code 219.434
Monitoring Requirements
Section 219
Section 219.434 Monitoring
Requirements
a) The owner or operator of a source subject to the control
requirements in Section 219.432 of this Subpart that uses an incinerator to
comply with the VOM emission limitation specified in Section 219.432(a)(1)
shall install, calibrate, maintain, and operate, according to manufacturer's
specifications, a temperature monitoring device equipped with a continuous
recorder and having an accuracy of
+
1 percent of the temperature
measured expressed in degress Celsius, or
+
0.5°C, whichever is greater.
1) Where an incinerator other than a catalytic incinerator is
used, a temperature monitoring device shall be installed in the firebox.
2) Where a catalytic incinerator is used, temperature monitoring
devices shall be installed in the gas stream immediately before and after the
catalyst bed.
b) The owner or operator of a source that uses a flare to comply
with Section 219.432(a)(2) of this Subpart shall install, calibrate, maintain,
and operate, according to manufacturer's specifications, a heat-sensing device,
such as an ultraviolet beam sensor or thermocouple, at the pilot light to
indicate continuous presence of a flame.
c) The owner or operator of a source that uses a boiler or
process heater with a design heat input capacity less than 44 megawatts to
comply with Section 219.432(a)(1) of this Subpart shall install, calibrate,
maintain, and operate, according to the manufacturer's specifications, a
temperature monitoring device in the firebox. The monitoring device shall be
equipped with a continuous recorder with an accuracy of
+
1 percent of
the temperature being measured expressed in degrees Celsius or
+
0.5°C,
whichever is greater. Any boiler or process heater in which all vent streams
are introduced with primary fuel is exempt from this requirement.
d) The owner or operator of a process vent with a TRE index value
of 4.0 or less that uses one or more product recovery devices shall install
either an organic monitoring device equipped with a continuous recorder or the
monitoring equipment specified in subsection (d)(1), (d)(2), (d)(3), or (d)(4)
of this Section, depending on the type of recovery device used. All monitoring
equipment shall be installed, calibrated, and maintained according to the
manufacturer's specifications.
1) Where an absorber is the final recovery device in the recovery
system, a scrubbing liquid temperature monitoring device and a specific gravity
monitoring device, each equipped with a continuous recorder, shall be used.
2) Where a condenser is the final recovery device in the recovery
system, a condenser exit (product side) temperature monitoring device equipped
with a continuous recorder and having an accuracy of
+
1 percent of the
temperature being monitored expressed in degrees Celsius or
+
0.5°C,
whichever is greater.
3) Where a carbon adsorber is the final recovery device in the
recovery system, an integrating regeneration steam flow monitoring device
having an accuracy of
+
10 percent, capable of recording the total
regeneration steam mass flow for each regeneration cycle; and a carbon bed
temperature monitoring device having an accuracy of
+
1 percent of the
temperature being monitored expressed in degrees Celsius of
+
0.5°C,
capable of recording the carbon bed temperature after each regeneration and
within 15 minutes of completing any cooling cycle.
4) Where a scrubber is used with an incinerator, boiler, or, in
the case of halogenated vent streams, a process heater, the following
monitoring equipment is required for the scrubber:
A) A pH monitoring device equipped with a continuous recorder to
monitor the pH of the scrubber effluent; and
B) Flow meters equipped with a continuous recorder at the scrubber
influent for liquid flow and the scrubber inlet for gas stream flow.
e) The owner or operator of a process vent using a vent system
that contains bypass lines capable of diverting a vent stream away from the
control device associated with a process vent shall comply with either (e)(1)
or (e)(2) of this Section. Equipment needed for safety purposes, including, but
not limited to, pressure relief devices, are not subject to this subsection.
1) The owner or operator shall install, calibrate, maintain, and
operate a flow indicator that provides a record of vent stream flow at least
once every 15 minutes. The flow indicator shall be installed at the entrance
to any bypass line that could divert the vent stream away from the control
device to the atmosphere.
2) The owner or operator shall secure the bypass line valve in
the closed position with a car-seal or a lock-and-key type configuration. A
visual inspection of the seal or closure mechanism shall be performed at least
once every month to ensure that the valve is maintained in the closed position
and the vent stream is not diverted through the bypass line.
f) The owner or operator of a process vent may monitor by an
equivalent alternative means or parameters other than those listed in
subsections (a) through (d) of this Section. Any equivalent alternative shall
be approved by the Agency and USEPA, and contained in the source's operating
permit as federally enforceable permit conditions.