35 Ill. Adm. Code 225.240
General Monitoring and Reporting Requirements
Section 225.240 General Monitoring and Reporting
Requirements
Except as otherwise indicated in this Subpart, the owner or
operator of an EGU must comply with the monitoring, recordkeeping, and
reporting requirements as provided in this Section, Sections 225.250 through
225.290 of this Subpart B, and Sections 1.14 through 1.18 of Appendix B to this
Part. If the EGU utilizes a common stack with units that are not EGUs and the
owner or operator of the EGU does not conduct emissions monitoring in the duct
to the common stack from each EGU, the owner or operator of the EGU must
conduct emissions monitoring in accordance with Section 1.16(b)(2) of Appendix
B to this Part and this Section, including monitoring in the duct to the
common stack from each unit that is not an EGU, unless the owner or operator of
the EGU counts the combined emissions measured at the common stack as the mass
emissions of mercury for the EGUs for recordkeeping and compliance purposes.
a) Requirements
for installation, certification, and data accounting. The owner or operator of
each EGU must:
1) Install
all monitoring systems required pursuant to this Section and Sections 225.250
through 225.290 for monitoring mercury mass emissions (including all systems
required to monitor mercury concentration, stack gas moisture content, stack
gas flow rate, and CO
2
or O
2
concentration, as
applicable, in accordance with Sections 1.15 and 1.16 of Appendix B to this
Part).
2) Successfully
complete all certification tests required pursuant to Section 225.250 and meet
all other requirements of this Section, Sections 225.250 through 225.290, and Sections
1.14 through 1.18
of Appendix B to this Part applicable to the
monitoring systems required under subsection (a)(1) of this Section.
3) Record,
report, and assure the quality of the data from the monitoring systems required
under subsection (a)(1) of this Section.
4) If
the owner or operator elects to use the low mass emissions excepted monitoring
methodology for an EGU that emits no more than 464 ounces (29 pounds) of
mercury per year pursuant to Section 1.15(b) of Appendix B to this Part, it
must perform emissions testing in accordance with Section 1.15(c) of Appendix B
to this Part to demonstrate that the EGU is eligible to use this excepted
emissions monitoring methodology, as well as comply with all other applicable
requirements of Section 1.15(b) through (f)
of Appendix B to this Part.
Also, the owner or operator must submit a copy of any information required to
be submitted to the USEPA pursuant to these provisions to the Agency. The
initial emissions testing to demonstrate eligibility of an EGU for the low mass
emissions excepted methodology must be conducted by the applicable of the following
dates:
A) If the
EGU has commenced commercial operation before July 1, 2008, at least by July 1,
2009, or 45 days prior to relying on the low mass emissions excepted
methodology, whichever date is later.
B) If the
EGU has commenced commercial operation on or after July 1, 2008, at least 45
days prior to the applicable date specified pursuant to subsection (b)(2) of
this Section or 45 days prior to relying on the low mass emissions excepted
methodology, whichever date is later.
b) Emissions
Monitoring Deadlines. The owner or operator must meet the emissions monitoring
system certification and other emissions monitoring requirements of subsections
(a)(1) and (a)(2) of this Section on or before the applicable of the following
dates. The owner or operator must record, report, and quality-assure the data
from the emissions monitoring systems required under subsection (a)(1) of this
Section on and after the applicable of the following dates:
1) For
the owner or operator of an EGU that commences commercial operation before July
1, 2008, by July 1, 2009, except that an EGU in an MPS Group for which an SO
2
scrubber or fabric filter is being installed to be in operation by December 31,
2009, as described in Section 225.233(c)(1)(A), shall have a date of January 1,
2010.
2) For
the owner or operator of an EGU that commences commercial operation on or after
July 1, 2008, by 90 unit operating days or 180 calendar days, whichever occurs
first, after the date on which the EGU commences commercial operation.
3) For
the owner or operator of an EGU for which construction of a new stack or flue
or installation of add-on mercury emission controls, a flue gas desulfurization
system, a selective catalytic reduction system, a fabric filter, or a compact
hybrid particulate collector system is completed after the applicable deadline pursuant
to subsection (b)(1) or (b)(2) of this Section, by 90 unit operating days or
180 calendar days, whichever occurs first, after the date on which emissions
first exit to the atmosphere through the new stack or flue, add-on mercury
emission controls, flue gas desulfurization system, selective catalytic
reduction system, fabric filter, or compact hybrid particulate collector
system.
4) For
an owner or operator of an EGU that originally elected to demonstrate
compliance pursuant to the emissions testing requirements in Section 225.239,
by the first day of the calendar quarter following the last emissions test
demonstrating compliance with Section 225.239.
c) The owner
or operator of an EGU that does not meet the applicable emissions monitoring
date set forth in subsection (b) of this Section for any emissions monitoring
system required pursuant to subsection (a)(1) of this Section must
begin
periodic emissions testing in accordance with Section 225.239.
d) Prohibitions.
1) No
owner or operator of an EGU may use any alternative emissions monitoring
system, alternative reference method for measuring emissions, or other
alternative to the emissions monitoring and measurement requirements of this
Section and Sections 225.250 through 225.290, unless such alternative is submitted
to the Agency in writing and approved in writing by the Manager of the Bureau
of Air’s Compliance Section, or his or her designee.
2) No
owner or operator of an EGU may operate its EGU so as to discharge, or allow to
be discharged, mercury emissions to the atmosphere without accounting for such
emissions in accordance with the applicable provisions of this Section,
Sections 225.250 through 225.290, and Sections 1.14 through 1.18
of
Appendix B to this Part, unless demonstrating compliance pursuant to Section
225.239, as applicable.
3) No
owner or operator of an EGU may disrupt the CEMS (or excepted monitoring
system), any portion thereof, or any other approved emission monitoring method,
and thereby avoid monitoring and recording mercury mass emissions discharged
into the atmosphere, except for periods of recertification or periods when
calibration, quality assurance testing, or maintenance is performed in
accordance with the applicable provisions of this Section, Sections 225.250
through 225.290, and Sections 1.14 through 1.18 of Appendix B to this Part.
4) No
owner or operator of an EGU may retire or permanently discontinue use of the CEMS
(or excepted monitoring system) or any component thereof, or any other approved
monitoring system pursuant to this Subpart B, except under any one of the
following circumstances:
A) The
owner or operator is monitoring emissions from the EGU with another certified
monitoring system that has been approved, in accordance with the applicable
provisions of this Section, Sections 225.250 through 225.290 of this Subpart B,
and Sections 1.14 through 1.18 of Appendix B to this Part, by the Agency for
use at that EGU and that provides emission data for the same pollutant or
parameter as the retired or discontinued monitoring system; or
B) The
owner or operator submits notification of the date of certification testing of
a replacement monitoring system for the retired or discontinued monitoring
system in accordance with Section 225.250(a)(3)(A).
C) The
owner or operator is demonstrating compliance pursuant to the applicable
subsections of Section 225.239.
e) Long-term Cold Storage.
The owner or operator of an EGU
that is in long-term cold storage is subject to the provisions of 40 CFR 75.4
and 40 CFR 75.64, incorporated by reference in Section 225.140, relating to monitoring,
recordkeeping, and reporting for units in long-term cold storage.