35 Ill. Adm. Code 370.1021
Dechlorination
Section 370
Section 370.1021
Dechlorination
a) General
Dechlorination of sewage plant effluents may be required to
reduce toxicity due to chlorine residuals.
b) Feed Equipment
1) Type
The common types of dechlorination feed equipment using
sulfur compounds include:
A) Vacuum solution feed of sulfur dioxide gas.
B) Positive displacement pump feed or aqueous solutions of sulfite
or bisulfite products.
2) Selection of Feed Equipment
The selection of the type of feed equipment using sulfur
compounds shall include consideration of operator safety and overall public
safety relative to the proximity of the sewage treatment plant to populated
areas and the security of the gas cylinder storage. The selection and design
of sulfur dioxide feeding equipment shall take into account the fact that the
gas reliquifies very easily.
c) Output Capacity of Sulfur Dioxide Cylinders
The number of feed cylinders or containers necessary to meet
the design delivery rates shall be based on the physical, thermodynamic and
chemical properties for sulfur dioxide. Refer to the Compressed Gas
Association publication CGA G-3-1988 "Sulfur Dioxide" or other
standard reference sources for information on sulfur dioxide properties.
d) Standby Equipment and Spare Parts
Standby equipment should be available of sufficient capacity
to replace the largest unit during shutdown. Spare parts to replace parts that
are subject to wear and breakage shall be available for all sulfonators.
e) Potable Water Supply
An ample supply of water shall be available for operating the
sulfonator. Where a booster pump is required duplicate equipment should be
provided and, when necessary, standby power. (Refer to Section
370.550(a)(4).) Protection of the potable water supply shall conform to the
requirements of Section 370.550(b)(6). In-line back flow preventers may not be
used.
f) Sulfur Dioxide Gas Supply
1) Cylinders
The use of 1-ton containers should be considered where the
average daily sulfur dioxide consumption is over 150 pounds. All upright
sulfur dioxide cylinders shall be strapped securely to prevent tipping.
2) Tank Cars
A) The use of tank cars, generally accompanied by evaporators, may
be considered for large installations. Areawide public safety shall be
evaluated as part of the considerations. Continuity of sulfur dioxide supply
shall be maintained during tank car switching.
B) The tank car being used for the sulfur dioxide supply shall be
located on a dead end, level track that is a dedicated siding. The tank car
shall be protected from accidental bumping by other railway cars by a locked
de-rail device, a closed lock switch, or both. The area shall be clearly
posted "DANGER SULFUR DIOXIDE." The tank car shall be secured by
adequate fencing with locked gates for personnel and rail access.
C) The tank car site shall be provided with an operating platform
at the unloading point that allows for easy access to the protective housing on
the tank car for flexible feed line connection and valve operation. Area lighting
adequate for night time operation and maintenance shall be provided.
3) Scales
A) Scales shall be provided for weighing cylinders or containers
at all plants using sulfur dioxide gas.
B) At large plants indicating and recording scales are
recommended. At a minimum, a platform scale shall be provided. Scales shall
be made of corrosion resistant material. Scales should be recessed unless
hoisting equipment is provided or the scales are low enough to allow the
cylinders to be rolled onto them.
4) Evaporator
Where the manifolding of several cylinders or containers will
be required to evaporate sufficient sulfur dioxide, consideration should be
given to liquid drawoff and installation of an evaporator. A liquid nitrogen
gas padding system to enhance the liquid sulfur dioxide delivery rate should be
considered.
5) Leak Detection and Controls
Sulfur dioxide leak detection equipment shall be provided
which has a sensitivity level equal to that of ambient air pollution monitoring
equipment. Where cylinders, one-ton containers and tank cars are used, a leak
repair kit that is compatible for use with sulfur dioxide gas shall be
provided. Leak repair kits used for chlorine gas (Section 370.1020(f)(5))
equipped with gasket materials suitable for service with sulfur dioxide may be
used. (See paragraphs 10.4 and 13.2 of "Sulfur Dioxide," Compressed
Gas Association, Inc., Publication CGA G-3-1988 for a discussion of suitable
materials.) Refer to Section 370.560.
g) Piping and Connections
1) Piping systems should be as simple as possible, with a minimum
number of joints, and shall be suitable for sulfur dioxide service. Piping
should be well supported and protected against temperature extremes.
2) The piping for the sulfur dioxide system shall be color-coded
and labeled to distinguish it from chlorine piping, and the system shall be
designed so that interconnections with chlorine piping cannot occur.
h) Housing
1) Container and Equipment Location
Containers and feed equipment should be located inside a fire
resistant building. Gas cylinders and containers should be protected from
direct sunlight.
A) Isolation
If gas sulfonation equipment and sulfur dioxide cylinders
will be located in a building also used for other purposes, the sulfur dioxide
equipment and containers shall be located in an isolated room that shall not
contain any chlorination equipment, chlorine containers or any other equipment
unrelated to sulfonation. Common walls to other areas of the building shall be
gastight. Doors to the room shall open only to the outside and shall be
equipped with panic hardware. Rooms shall be at ground level and shall allow
easy access to all equipment. Storage areas should be separated from feed
areas; sulfur dioxide and chlorine cylinders shall be stored in separate areas.
B) Inspection Window
A clear gastight window shall be installed in the sulfonate
room to permits the units to be viewed and gauges to be read without entering
the room.
2) Heat
Sulfonator housing facilities shall be provided with a means
of heating so that cylinder temperatures can be maintained in the range of 90
to 100° F when sulfur dioxide is to be withdrawn from the cylinder. The
sulfonator room shall be protected from excessive heat.
3) Ventilation for Sulfur Dioxide Systems
A) Forced, mechanical ventilation that will provide one complete
air change per minute shall be installed in the sulfonator room. The entrance
to the exhaust duct from the room shall be within 12 inches from the floor and
the point of discharge shall be located so as not to contaminate the air in the
immediate vicinity of the door to the sulfonator room or ventilation inlet to
any buildings or inhabited areas.
B) The air inlets to the sulfator room shall be located so as to
provide cross ventilation with air and at temperatures that will not adversely
affect the sulfonation equipment. The vent hose from the sulfonator shall
discharge to the outside atmosphere above grade.
4) Electrical Controls
Controls for fans and lights shall be located at the
entrances to the sulfonation room and shall automatically operate when the door
is opened and continue in operation when the operator enters the room and the
door is closed. Provision shall be made for operation of the fans and lights
from the outside without opening the door.
i) Respiratory Protection Equipment
Respiratory protection equipment meeting the requirements of
NIOSH shall be available at all installations where sulfur dioxide gas is
handled and shall be stored in a convenient location outside of any room where
sulfur dioxide is used or stored. The units shall use compressed air, shall
have at least a 30-minute capacity and shall be the same as or compatible with
NIOSH-approved units used by the local fire department. Instructions for
using, testing and replacing mask parts shall be posted. At large
installations, providing acid suits and fire suits should be considered.
j) Application of Sulfonation Chemicals
1) Contact Period and Reaeration
A minimum contact period of 30 seconds, including mixing
time, at design peak hourly flow or maximum pumpage rate shall be provided.
Mechanical mixers are required unless the mixing facility will provide the
necessary hydraulic turbulence to assure thorough mixing. A means of
reaeration shall be provided to insure maintenance of the required dissolved
oxygen concentration in the effluent and the receiving stream after
sulfonation. When choosing a reaeration method the fact that excess sulfur
dioxide, formed when the dechlorinating chemicals are dissolved in water, may
be expected to consume 1 mg of dissolved oxygen for every 4 mg of sulfur
dioxide should be taken into account.
2) Sulfonation Dosing Rate Capacity
A) Capacity
Sulfonators shall be designed to have a capacity adequate to
produce an effluent that meets the applicable chlorine residual effluent
limits. Where necessary to meet the operating ranges, multiple units shall be
provided for adequate peak capacity and to provide a sufficiently low feed rate
on turn down to avoid depletion of the dissolved oxygen concentrations in the
receiving waters. The sulfonator system shall be designed on a rational basis
and calculations justifying the equipment sizing and number of units shall be
submitted for the entire operating range, including the minimum turn down
capability for the type of control to be used. System considerations shall
include the sensitivity and location of the controlling sewage flow meter, the
telemetering equipment and sulfonator controls.
B) Dosing Rates
The design dosage rate of the sulfonation equipment shall be
based on the particular dechlorinating chemical used and the applicable
residual chlorine limits. The following theoretical amounts of the commonly
used dechlorinating chemicals may be used for initial approximations to size
feed equipment.
Theoretical
mg/l required to neutralize 1 mg/l Cl
2
Sulfur dioxide (gas)
0.90
Sodium meta bisulfite
(solution)
1.34
Sodium bisulfite (solution)
1.46
The design
shall take into account the fact that under good mixing conditions
approximately 10% more dechlorinating chemical than theoretical value is
required for satisfactory results.
C) Liquid Solution Tanks
Mixing and dilution tanks for dechlorinating feed solutions
shall be provided as necessary to mix dry compounds and to dilute liquid
compounds to provide for proper dosage. Solution tanks should be covered to
minimize evaporation. The mixing and dilution tanks should be sized to provide
sufficient feed solution for several days of operation. The tanks shall be
made of materials that will withstand the corrosive nature of the solutions.
Refer to Section 370.560.