35 Ill. Adm. Code 370.211
Design Flows
Section 370
Section 370.211 Design Flows
The following flows shall be
identified in the basis of design for sewers, lift stations, sewage treatment
plants, treatment units and other wastewater handling facilities.
a) Design Average Flow
The design
average flow is the average of the daily volumes to be received for a
continuous 12-month period of the design year, expressed as a volume per unit
of time.
b) Design Maximum Flow
The design
maximum flow is the largest volume of flow to be received during a continuous
24-hour period, expressed as a volume per unit of time.
c) Design Peak Hourly Flow
The design
peak hourly flow is the largest volume of flow to be received during a one hour
period, expressed as a volume per unit of time.
d) Design Peak Flow
The design
peak flow is the instantaneous maximum flowrate to be received.