35 Ill. Adm. Code 370.310
Design Basis
Section 370
Section 370.310 Design Basis
a) Per Capita Flow
1) New Sewers for Undeveloped Areas
New sewer
systems to serve currently undeveloped areas shall be designed on the basis of
a design average flow of not less than 100 gallons per capita per day which is
assumed to cover normal infiltration, but an additional allowance should be
made where conditions are unfavorable.
2) New Sewers for Existing Developed Areas
For new sewers
designed to serve existing developed areas, the design average flow per capita
(100 gpd) shall be appropriately increased to allow for inflow/infiltration
contributions from the existing buildings other than roof and foundation drains
which shall be excluded in accordance with Section 370.121(a).
b) Design Peak Flow
1) The design peak flow for sanitary sewers shall be selected
based on one of the following methods:
A) The ratio of peak to average daily flow as determined from
Appendix D, Figure No. 1.
B) Values established from an infiltration/inflow study acceptable
to the Agency.
2) Use of other values for the design peak flow will be
considered if justified on the basis of extensive documentation.
3) Combined Sewer Interceptors
Intercepting
sewers, in the case of combined sewer systems, should fulfill the above
requirements for sewers and have sufficient additional capacity to transport
the increment of combined sewage required by the IPCB Regulations.
c) Alternate Methods
When
deviations from subsections (a) and (b) are proposed, a description of the
procedure used for sewer design shall be included in the submission of plan
documents.
d) Basis of Design and Calculations
The basis of
design for all sewer projects shall accompany the plan documents. Calculations
shall be submitted to show that sewers will have sufficient hydraulic capacity
to transport the design peak flows.