35 Ill. Adm. Code 370.620
Grit Removal Facilities
Section 370
Section 370.620 Grit Removal
Facilities
a) Where Required
Grit removal facilities should be provided for all sewage
treatment plants and are required for plants receiving sewage from combined
sewers or from sewer systems receiving substantial amounts of grit. If a plant
serving a separate sewer system is designed without grit removal facilities,
the design shall include provision for future installation. Consideration
shall be given to possible damaging effects on pumps, and other preceding
equipment, and the need for additional storage capacity in treatment units
where grit is likely to accumulate.
b) Location
Grit removal facilities should be located ahead of pumps. In
such cases, coarse bar racks should be placed ahead of mechanically cleaned
grit removal facilities. Comminution equipment, when used, shall be located
downstream of the grit facility in order to reduce the operation and
maintenance problems associated with grit.
c) Type and number of units
1) The selection of the type of grit removal shall be based on
necessary flexibility of velocity control to remove the selected size grit
particulates through the range of expected plant flows, the volume of grit
expected, and available area and hydraulic gradient limits at the site. Aerated
or area type grit removal units equipped with adequate controls for operational
flexibility are recommended where flow rates and grit characteristics and
volume are expected to vary widely.
2) Plants treating wastes from combined sewers shall have at
least one, preferably two or more, mechanically cleaned grit removal units,
with provision for unit bypassing. A single manually cleaned or mechanically
cleaned grit chamber with unit bypass is acceptable for small sewage treatment
plants serving separate sanitary sewer systems. Minimum facilities for larger
plants serving separate sanitary sewers shall be at least one mechanically
cleaned unit with a unit bypass.
d) Design Factors
1) Channel Type Units
A) Turbulence Control
The equipment and inlet and outlet structures shall be
designed to minimize turbulance throughout the channel.
B) Velocity and Detention
Channel-type chambers shall be designed to provide controlled
velocities as close as possible to 1 foot per second. The detention period
shall be based on the size of particle to be removed.
2) Aerated Units
A) Inlet
The inlet shall be located and arranged to prevent short
circuiting to the outlet and oriented to the unit flow pattern so as to provide
for adequate scouring segregation of organic and grit materials prior to
discharge.
B) Detention
A detention time of at least 3 minutes at design peak flow
should be provided.
C) Air Supply
Air should be supplied at 5 cubic feet per minute (cfm) per
foot of tank length. The rate of air supplied shall be widely variable so as
to maximize unit process effectiveness.
3) Grit Washing and Freeze Protection
All facilities not provided with positive velocity control
should include means for grit washing to further separate organic and inorganic
materials. Grit elevator and washing facilities shall be housed to prevent
freezing. Provision for adequate heating and ventilation shall be provided to
prevent corrosion.
4) Drains
Provisions should be made for dewatering each unit.
5) Water
An adequate supply of water under pressure shall be provided
for clean up.
e) Grit Removal
Grit removal facilities located in pits shall be provided
with mechanical equipment for pumping or hoisting grit to ground level. Pits
deeper than 4 feet shall be provided with stairway access. An approved-type
elevator or manlift may be desirable in some locations. Adequate ventilation,
as described in Section 370.600(a)(5), and lighting shall be provided for pits
that are deeper than 4 feet or are within an enclosed area.
f) Grit Handling
Impervious, non-slip, working surfaces with drains back to process
shall be provided for grit handling areas. Safety handrails shall be provided
around the working platform areas. If grit is to be transported, the conveying
equipment shall be designed to avoid loss of material and protection from
freezing. Grit disposal methods shall be in compliance with 35 Ill. Adm. Code
700 and shall be described in the plan documents.
g) Electrical
All electrical fixtures and controls in enclosed or below
grade grit removal areas where hazardous gases may accumulate shall meet the
requirements of the National Electrical Code (1996) for Class 1, Group D,
Division 1 locations.