35 Ill. Adm. Code 602.310
Projects Requiring Disinfection
Section 602.310 Projects Requiring
Disinfection
a) Wells, water storage tanks,
water treatment plants, and water mains must be disinfected in accordance with
AWWA C651, C652, C653, or C654, incorporated by reference in 35 Ill. Adm. Code
601.115.
b) Disinfection of a filter with
granular activated carbon (GAC) must be completed before adding the GAC.
Disinfection of an ion exchange unit must be completed before adding a resin
with a low chlorine tolerance. Disinfection of a membrane unit must be
completed before adding membrane material with a low chlorine tolerance. Care
should be taken when handling the GAC, resin, or membrane to keep the material
as clean as possible.
c) Except as provided in Section
602.315,
the
permit applicant must verify disinfection before seeking an operating
permit-by-rule under Section 602.235 or the issuance of an operating permit by
the Agency for completed construction projects. Disinfection
is verified when
two consecutive water sample sets collected from the completed project at least
24 hours apart
show
the absence of coliform bacteria and the presence of a chlorine residual as
required by 35 Ill. Adm. Code 604.725
. A sample set consists of the following:
1) For water mains, representative
water samples must be collected from every 1,200 feet of new main along each
branch and from the end of the line. The Agency may approve a different
sampling plan on a site-specific basis.
2) For water treatment plants,
representative water samples must be collected from each aerator, detention
tank, filter, ion exchange unit, and clearwell, from all other treatment
components other than those not requiring disinfection under Section 602.315,
and from the entry point to the distribution system.
d) Analyses conducted under this
Section must be performed by a certified laboratory.