35 Ill. Adm. Code 604.1415
System Design
Section 604.1415Â System Design
a)Â Â Â Â Â Â Â Â Pressure
1)Â Â Â Â Â Â Â Â The
system must be designed to maintain a minimum pressure of 20 psi at ground
level at all points in the distribution system under all conditions of flow.
2)Â Â Â Â Â Â Â Â The
normal working pressure on all transmission mains for finished water must be at
least 20 psi. All other water mains must have a normal working pressure of at
least 35 psi.
3)Â Â Â Â Â Â Â Â When
static pressures exceed 100 psi, pressure reducing devices must be provided on
water mains or on individual service lines.
4)Â Â Â Â Â Â Â Â All
water mains, including those not designed to provide fire protection, must be
sized after a hydraulic analysis based on flow demands and pressure
requirements.
b)Â Â Â Â Â Â Â Â Diameter of Water Mains
1)Â Â Â Â Â Â Â Â The
minimum size of water main that provides for fire protection and serving fire
hydrants must be of 6-inch diameter. Larger size mains will be required if
necessary to allow the withdrawal of the required fire flow while maintaining
the minimum residual pressure specified in subsection (a).
2)Â Â Â Â Â Â Â Â The
minimum size of water main must be 4-inch nominal diameter in distribution
systems serving incorporated areas, subdivisions or other closely situated
housing or commercial units.
3)Â Â Â Â Â Â Â Â The
minimum size of water main must be 3-inch nominal diameter in distribution
systems serving rural areas where service connections are widely spaced, water
usage per service is low, and rates of flow are slow.
c)Â Â Â Â Â Â Â Â Dead Ends
1)Â Â Â Â Â Â Â Â Dead
ends must be minimized.
2)Â Â Â Â Â Â Â Â Dead
end mains must be equipped with a means to provide adequate flushing as
provided in Section 604.1425(b)(1).