35 Ill. Adm. Code 604.250
Aquifer Types and Construction Methods
Section 604.250Â Aquifer Types and Construction Methods
a)Â Â Â Â Â Â Â Â Sand or Gravel Wells
1)Â Â Â Â Â Â Â Â Unless
otherwise approved by the Agency under Section 604.145(b), the permanent casing
and grout must extend at least 25 feet below the original ground elevation.
2)Â Â Â Â Â Â Â Â If a
temporary or a surface casing is used, it must be completely withdrawn.
b)Â Â Â Â Â Â Â Â Gravel Pack Material
1)Â Â Â Â Â Â Â Â Gravel
pack materials must:
A)Â Â Â Â Â Â Â be
sized based on sieve analysis of the formation; and
B)Â Â Â Â Â Â Â be
well-rounded particles of 95 percent siliceous material that are smooth and
uniform, free of foreign material, properly sized, and washed and then
disinfected immediately prior to or during placement.
2)Â Â Â Â Â Â Â Â Gravel
Pack
A)Â Â Â Â Â Â Â Gravel
pack must be placed in one continuous operation.
B)Â Â Â Â Â Â Â Gravel
pack must be placed in a manner that prevents segregation and gradation during
placement.
C)Â Â Â Â Â Â Â The
annular space between the well screen and the hole must allow for proper
placement of gravel pack.
D)Â Â Â Â Â Â Â Gravel
pack must extend above the highest well screen with an allowance for settling.
E)Â Â Â Â Â Â Â Protection
from leakage of grout into the gravel pack or screen must be provided.
F)Â Â Â Â Â Â Â Â Permanent
inner casing and outer casings must meet the requirements of Section
604.240(d).
3)Â Â Â Â Â Â Â Â Unless
otherwise approved by the Agency under Section 604.145(b), minimum permanent
casing and grouted depth must be at least 25 feet below the original ground
elevation.
c)Â Â Â Â Â Â Â Â Radial Water Collector
1)Â Â Â Â Â Â Â Â Locations
of all caisson construction joints and porthole assemblies must be indicated on
plans submitted to the Agency.
2)Â Â Â Â Â Â Â Â Provisions
must be made to assure that radial collectors are essentially horizontal.
3)Â Â Â Â Â Â Â Â Caisson
Construction
A)Â Â Â Â Â Â Â The
caisson wall must be reinforced to withstand the forces to which it will be
subjected.
B)Â Â Â Â Â Â Â The
top of the caisson must be extended at least above the flood plain of a
100-year flood or flood of record and covered with a watertight floor.
C)Â Â Â Â Â Â Â All
openings in the floor must be curbed and protected from entrance of foreign
material.
D)Â Â Â Â Â Â Â The
pump discharge piping must not be placed through the caisson walls.
d)Â Â Â Â Â Â Â Â Fractured or Highly
Permeable Bedrock Aquifer Wells
1)Â Â Â Â Â Â Â Â Where
the depth of unconsolidated formations is more than 50 feet over fractured or
highly permeable bedrock, the permanent casing must be firmly seated in rock.
2)Â Â Â Â Â Â Â Â Where
the depth of unconsolidated formations is less than 50 feet, the depth of
casing and grout must be at least 50 feet.