35 Ill. Adm. Code 604.410

Spray Aeration

Year: 2026Length: 74 wordsOfficial source
Section 604.410  Spray Aeration Spray aeration design must provide: a)         a hydraulic head of between 5 and 25 feet; b)         nozzles, with the size, number, and spacing of the nozzles being dependent on the flow rate, the space, and amount of head available; c)         nozzle diameters in the range of 1 to 1.5 inches to minimize clogging; and d)         an enclosed basin to contain the spray, with any openings protected by a 24-mesh screen.