35 Ill. Adm. Code 6110.611.382
Monitoring Requirements
Section 611
TITLE 35: ENVIRONMENTAL PROTECTION
SUBTITLE F: PUBLIC WATER SUPPLIES
CHAPTER I: POLLUTION CONTROL BOARD
PART 611 PRIMARY DRINKING WATER STANDARDS
SECTION 611.382 MONITORING REQUIREMENTS
Section 611.382 Monitoring
Requirements
a) General Requirements
1) A supplier must take all samples during normal operating
conditions.
2) A supplier may consider multiple wells drawing water from a
single aquifer as one treatment plant for determining the minimum number of
TTHM and HAA5 samples required with Agency approval.
3) Failure to monitor in compliance with the monitoring plan required
under subsection (f) is a monitoring violation.
4) If compliance is based on a running annual average of monthly
or quarterly samples or averages and the supplier's failure to monitor makes it
impossible to determine compliance with MCLs or MRDLs, this failure to monitor
will be treated as a violation for the entire period covered by the annual
average.
5) A supplier must use only data collected under the provisions
of this Subpart I to qualify for reduced monitoring.
b) Monitoring Requirements for Disinfection Byproducts (DBPs)
1) TTHMs and HAA5
A) Routine Monitoring. A supplier must monitor at the following frequency:
i) A
Subpart B system supplier that serves 10,000 or more persons must collect four
water samples per quarter per treatment plant. At least 25 percent of all
samples collected each quarter must be collected at locations representing
maximum residence time. The remaining samples may be taken at locations
representative of at least average residence time in the distribution system
and representing the entire distribution system, taking into account the number
of persons served, the different sources of water, and the different treatment
methods.
ii) A
Subpart B system supplier that serves from 500 to 9,999 persons must collect
one water sample per quarter per treatment plant. The samples must be
collected from locations representing maximum residence time.
iii) A
Subpart B system supplier that serves fewer than 500 persons must collect one
sample per year per treatment plant during month of warmest water temperature.
The samples must be collected from locations representing maximum residence
time. If the sample (or average of annual samples, if more than one sample is
taken) exceeds the MCL, the supplier must increase the monitoring frequency to
one sample per treatment plant per quarter, taken at a point reflecting the
maximum residence time in the distribution system, until the supplier meets the
standards in subsection (b)(1)(D).
iv) A
supplier that uses only groundwater not under direct influence of surface
water, that uses chemical disinfectant, and that serves 10,000 or more persons
must collect one water sample per quarter per treatment plant. The samples
must be collected from locations representing maximum residence time.
v) A
supplier that uses only groundwater not under direct influence of surface
water, that uses chemical disinfectant, and that serves fewer than 10,000
persons must collect one sample per year per treatment plant during month of
warmest water temperature. The samples must be collected from locations
representing maximum residence time. If the sample (or average of annual
samples, if more than one sample is taken) exceeds MCL, the supplier must
increase monitoring to one sample per treatment plant per quarter, taken at a
point reflecting the maximum residence time in the distribution system, until
the supplier meets standards in subsection (b)(1)(D).
BOARD NOTE:
If a supplier elects to sample more frequently than the minimum required, at
least 25 percent of all samples collected each quarter (including those taken
in excess of the required frequency) must be taken at locations that represent
the maximum residence time of the water in the distribution system. The
remaining samples must be taken at locations representative of at least average
residence time in the distribution system. For a supplier using groundwater
not under the direct influence of surface water, multiple wells drawing water
from a single aquifer may be considered one treatment plant for determining the
minimum number of samples required, with Agency approval.
B) A supplier may reduce monitoring, except as otherwise provided,
in compliance with the following:
i) A
Subpart B system supplier that serves 10,000 or more persons and that has a
source water annual average TOC level, before any treatment, of less than or
equal to 4.0 mg/ℓ may reduce monitoring if it has monitored for at least
one year and its TTHM annual average is less than or equal to 0.040 mg/ℓ
and HAA5 annual average is less than or equal to 0.030 mg/ℓ. The reduced
monitoring allowed is a minimum of one sample per treatment plant per quarter
at a distribution system location reflecting maximum residence time.
ii) A
Subpart B system supplier that serves from 500 to 9,999 persons and that has a
source water annual average TOC level, before any treatment, of less than or
equal to 4.0 mg/ℓ may reduce monitoring if it has monitored at least one
year and its TTHM annual average is less than or equal to 0.040 mg/ℓ and
HAA5 annual average is less than or equal to 0.030 mg/ℓ. The reduced
monitoring allowed is a minimum of one sample per treatment plant per year at a
distribution system location reflecting maximum residence time during month of
warmest water temperature.
BOARD NOTE: Any Subpart B system
supplier that serves fewer than 500 persons may not reduce its monitoring to
less than one sample per treatment plant per year.
iii) A
supplier using only groundwater not under direct influence of surface water
using chemical disinfectant and that serves 10,000 or more persons may reduce
monitoring if it has monitored at least one year and its TTHM annual average is
less than or equal to 0.040 mg/ℓ and HAA5 annual average is less than or
equal to 0.030 mg/ℓ. The reduced monitoring allowed is a minimum of one
sample per treatment plant per year at a distribution system location
reflecting maximum residence time during month of warmest water temperature.
iv) A
supplier using only groundwater not under direct influence of surface water that
uses chemical disinfectant and that serves fewer than 10,000 persons may reduce
monitoring if it has monitored at least one year and its TTHM annual average is
less than or equal to 0.040 mg/ℓ and HAA5 annual average is less than or
equal to 0.030 mg/ℓ for two consecutive years or TTHM annual average is less
than or equal to 0.020 mg/ℓ and HAA5 annual average is less than or equal
to 0.015 mg/ℓ for one year. The reduced monitoring allowed is a minimum
of one sample per treatment plant per three year monitoring cycle at a distribution
system location reflecting maximum residence time during month of warmest water
temperature, with the three-year cycle beginning on January 1 following the quarter
in which the supplier qualifies for reduced monitoring.
C
)
Monitoring Requirements
for Source Water TOC. In order to qualify for reduced monitoring for TTHM and
HAA5 under subsection (b)(1)(B), a Subpart B system supplier not monitoring
under the provisions of subsection (d) must take monthly TOC samples every 30
days at a location prior to any treatment. In addition to meeting other
criteria for reduced monitoring in subsection (b)(1)(B), the source water TOC
running annual average must be
£
4.0
mg/ℓ (based on the most recent four quarters of monitoring) on a
continuing basis at each treatment plant to reduce or remain on reduced
monitoring for TTHM and HAA5. Once qualified for reduced monitoring for TTHM
and HAA5 under subsection (b)(1)(B), a system may reduce source water TOC
monitoring to quarterly TOC samples taken every 90 days at a location prior to any
treatment.
D) A Subpart B system supplier on a reduced monitoring schedule
may remain on that reduced schedule as long as the average of all samples taken
in the year (for a supplier that must monitor quarterly) or the result of the
sample (for a supplier that must monitor no more frequently than annually) is
no more than 0.060 mg/ℓ and 0.045 mg/ℓ for TTHMs and HAA5,
respectively. A supplier that does not meet these levels must resume
monitoring at the frequency identified in subsection (b)(1)(A) in the quarter
immediately following the monitoring period in which the supplier exceeds 0.060
mg/ℓ for TTHMs or 0.045 mg/ℓ for HAA5. For a supplier that uses
only groundwater not under the direct influence of surface water and that
serves fewer than 10,000 persons, if either the TTHM annual average is greater
than 0.080 mg/ℓ or the HAA5 annual average is greater than 0.060 mg/ℓ,
the supplier must go to increased monitoring identified in subsection (b)(1)(A)
in the quarter immediately following the monitoring period in which the
supplier exceeds 0.080 mg/ℓ for TTHMs or 0.060 mg/ℓ for HAA5.
E) The Agency may return a supplier to routine monitoring.
2) Chlorite. A CWS or NTNCWS supplier using chlorine dioxide,
for disinfection or oxidation, must conduct monitoring for chlorite.
A) Routine Monitoring
i) Daily Monitoring. A supplier must take daily samples at the
entrance to the distribution system. For any daily sample that exceeds the
chlorite MCL, the supplier must take additional samples in the distribution
system the following day at the locations required by subsection (b)(2)(B), in
addition to the sample required at the entrance to the distribution system.
ii) Monthly Monitoring. A supplier must take a three-sample set
each month in the distribution system. The supplier must take one sample at
each of the following locations: near the first customer, at a location
representative of average residence time, and at a location reflecting maximum
residence time in the distribution system. Any additional routine sampling
must be conducted in the same manner (as three-sample sets, at the specified
locations). The supplier may use the results of additional monitoring
conducted under subsection (b)(2)(B) to meet the requirement for monitoring in
this subsection (b)(2)(A)(ii).
B) Additional Monitoring. On each day following a routine sample
monitoring result that exceeds the chlorite MCL at the entrance to the
distribution system, the supplier must take three chlorite distribution system
samples at the following locations: as close to the first customer as possible,
in a location representative of average residence time, and as close to the end
of the distribution system as possible (reflecting maximum residence time in
the distribution system).
C) Reduced Monitoring
i) Chlorite monitoring at the entrance to the distribution
system required by subsection (b)(2)(A)(i) may not be reduced.
ii) Chlorite monitoring in the distribution system required by
subsection (b)(2)(A)(ii) may be reduced to one three-sample set per quarter
after one year of monitoring if no individual chlorite sample taken in the
distribution system under subsection (b)(2)(A)(ii) has exceeded the chlorite
MCL and the supplier has not been required to conduct monitoring under
subsection (b)(2)(B). The supplier may remain on the reduced monitoring
schedule until either any of the three individual chlorite samples taken quarterly
in the distribution system under subsection (b)(2)(A)(ii) exceeds the chlorite
MCL or the supplier is required to conduct monitoring under subsection
(b)(2)(B), at which time the supplier must revert to routine monitoring.
3) Bromate
A) Routine Monitoring. A CWS or NTNCWS supplier using ozone, for
disinfection or oxidation, must take one sample per month for each treatment
plant in the system using ozone. A supplier must take samples monthly at the
entrance to the distribution system while the ozonation system is operating
under normal conditions.
B) Reduced Monitoring. A supplier required to analyze for bromate
may reduce monitoring from monthly to quarterly if the supplier's running
annual average bromate concentration is not greater than 0.0025 mg/ℓ
based on monthly bromate measurements under subsection (b)(3)(A) for the most
recent four quarters, with samples analyzed using USEPA 302.0 (09), USEPA 317.0
(01), USEPA 321.8 (97), USEPA 326.0 (02), or USEPA 557 (09), each incorporated
by reference in Section 611.102. If a supplier has qualified for reduced
bromate monitoring under subsection (b)(3)(B)(i), that supplier may remain on
reduced monitoring as long as the running annual average of quarterly bromate
samples not greater than 0.0025 mg/ℓ based on samples analyzed using
USEPA 302.0 (09), USEPA 317.0 (01), USEPA 321.8 (97), 326.0 (02), or USEPA 557 (09).
If the running annual average bromate concentration is greater than 0.0025
mg/ℓ, the supplier must resume routine monitoring required by subsection
(b)(3)(A).
c) Monitoring
Requirements for Disinfectant Residuals
1) Chlorine and Chloramines
A) Routine Monitoring. A CWS or NTNCWS supplier that uses
chlorine or chloramines must measure the residual disinfectant level in the distribution
system at the same point in the distribution system and at the same time as
total coliforms are sampled, as specified in Sections 611.1054 through
611.1058. A Subpart B system supplier may use the results of residual
disinfectant concentration sampling conducted under Section 611.532 for
unfiltered systems or Section 611.533 for systems that filter, in lieu of
taking separate samples.
B) Reduced Monitoring. Monitoring may not be reduced.
2) Chlorine Dioxide
A) Routine Monitoring. A CWS, an NTNCWS, or a transient non-CWS
supplier that uses chlorine dioxide for disinfection or oxidation must take
daily samples at the entrance to the distribution system. For any daily sample
that exceeds the MRDL, the supplier must take samples in the distribution
system the following day at the locations required by subsection (c)(2)(B), in
addition to the sample required at the entrance to the distribution system.
B) Additional Monitoring. On each day following a routine sample
monitoring result that exceeds the MRDL, the supplier must take three chlorine
dioxide distribution system samples. If chlorine dioxide or chloramines are
used to maintain a disinfectant residual in the distribution system, or if
chlorine is used to maintain a disinfectant residual in the distribution system
and there are no disinfection addition points after the entrance to the
distribution system (i.e., no booster chlorination), the supplier must take
three samples as close to the first customer as possible, at intervals of at
least six hours. If chlorine is used to maintain a disinfectant residual in
the distribution system and there are one or more disinfection addition points
after the entrance to the distribution system (i.e., booster chlorination), the
supplier must take one sample at each of the following locations: as close to
the first customer as possible, in a location representative of average
residence time, and as close to the end of the distribution system as possible
(reflecting maximum residence time in the distribution system).
C) Reduced Monitoring. Monitoring may not be reduced.
d) Monitoring Requirements for Disinfection Byproduct (DBP) Precursors
1) Routine Monitoring. A Subpart B system supplier that uses
conventional filtration treatment (as defined in Section 611.101) must monitor
each treatment plant for TOC not past the point of combined filter effluent
turbidity monitoring and representative of the treated water. A supplier
required to monitor under this subsection (d)(1) must also monitor for TOC in
the source water prior to any treatment at the same time as monitoring for TOC
in the treated water. These samples (source water and treated water) are
referred to as paired samples. At the same time as the source water sample is
taken, a system must monitor for alkalinity in the source water prior to any
treatment. A supplier must take one paired sample and one source water
alkalinity sample per month per plant at a time representative of normal
operating conditions and influent water quality.
2) Reduced Monitoring. A Subpart B system supplier with an
average treated water TOC of less than 2.0 mg/ℓ for two consecutive
years, or less than 1.0 mg/ℓ for one year, may reduce monitoring for both
TOC and alkalinity to one paired sample and one source water alkalinity sample
per plant per quarter. The supplier must revert to routine monitoring in the
month following the quarter when the annual average treated water TOC greater
than or equal to 2.0 mg/ℓ.
e) Bromide. A supplier required to analyze for bromate may
reduce bromate monitoring from monthly to once per quarter, if the supplier
demonstrates that the average source water bromide concentration is less than
0.05 mg/ℓ based upon representative monthly measurements for one year.
The supplier must continue bromide monitoring to remain on reduced bromate
monitoring.
f) Monitoring Plans. Each supplier required to monitor under
this Subpart I must develop and implement a monitoring plan. The supplier must
maintain the plan and make it available for inspection by the Agency and the
general public no later than 30 days following the applicable compliance dates
in Section 611.380(b). A Subpart B system supplier that serves more than 3,300
persons must submit a copy of the monitoring plan to the Agency no later than
the date of the first report required under Section 611.384. After review, the
Agency may require changes in any plan elements. The plan must include at
least the following elements:
1) Specific locations and schedules for collecting samples for
any parameters included in this Subpart I;
2) How the supplier will calculate compliance with MCLs, MRDLs,
and treatment techniques; and
3) If approved for monitoring as a consecutive system, or if
providing water to a consecutive system, under the provisions of Section
611.500, the sampling plan must reflect the entire distribution system.
BOARD NOTE: Derived from 40 CFR
141.132.