35 Ill. Adm. Code 6110.611.953
Disinfection Profile
TITLE 35: ENVIRONMENTAL PROTECTION
SUBTITLE F: PUBLIC WATER SUPPLIES
CHAPTER I: POLLUTION CONTROL BOARD
PART 611 PRIMARY DRINKING WATER STANDARDS
SECTION 611.953 DISINFECTION PROFILE
Section 611.953 Disinfection
Profile
a) Applicability. A
disinfection profile is a graphical representation of a system's level of
Giardia lamblia or virus inactivation measured during the course of a year. A
Subpart B community or non-transient non-community water system supplier that
serves fewer than 10,000 persons must develop a disinfection profile unless the
Agency, by a SEP, determines that a profile is unnecessary. The Agency may
approve the use of a more representative data set for disinfection profiling
than the data set required under subsections (c) through (g).
b) Determination That a Disinfection
Profile Is Not Necessary. The Agency may only determine that a disinfection
profile is not necessary if the system's TTHM and HAA5 levels are below 0.064
mg/ℓ and 0.048 mg/ℓ, respectively. To determine these levels, TTHM
and HAA5 samples must have been collected during the month with the warmest
water temperature, and at the point of maximum residence time in the
distribution system. The Agency may, by a SEP, approve the use of a different
data set to determine these levels if it determines that the data set is representative
TTHM and HAA5 data.
c) Development of a Disinfection
Profile. A disinfection profile consists of the following three steps:
1) First, the supplier must
collect data for several parameters from the plant, as discussed in subsection
(d), over the course of 12 months;
2) Second, the supplier
must use this data to calculate weekly log inactivation as discussed in
subsections (e) and (f); and
3) Third, the supplier must
use these weekly log inactivations to develop a disinfection profile as specified
in subsection (g).
d) Data Required for a Disinfection
Profile. A supplier must monitor the following parameters to determine the
total log inactivation using the analytical methods in Section 611.531, once
per week on the same calendar day, over 12 consecutive months:
1) The temperature of the
disinfected water at each residual disinfectant concentration sampling point
during peak hourly flow;
2) If a supplier uses
chlorine, the pH of the disinfected water at each residual disinfectant concentration
sampling point during peak hourly flow;
3) The disinfectant contact
times ("T") during peak hourly flow; and
4) The residual
disinfectant concentrations ("C") of the water before or at the first
customer and prior to each additional point of disinfection during peak hourly
flow.
e) Calculations Based on
the Data Collected. The tables in Appendix B must be used to determine the
appropriate CT
99.9
value. The supplier must calculate the total
inactivation ratio as follows, and multiply the value by 3.0 to determine log
inactivation of Giardia lamblia:
1) If the supplier uses
only one point of disinfectant application, it must determine either of the
following:
A) One inactivation ratio
(CT
calc
/CT
99.9
) before or at the first customer during peak
hourly flow; or
B) Successive CT
calc
/CT
99.9
values, representing sequential inactivation ratios, between the point of
disinfectant application and a point before or at the first customer during
peak hourly flow. Under this alternative, the supplier must calculate the
total inactivation ratio by determining CT
calc
/CT
99.9
for
each sequence and then adding the CT
calc
/CT
99.9
values
together to determine
Σ
CT
calc
/CT
99.9
.
2) If the supplier uses
more than one point of disinfectant application before the first customer, it
must determine the CT
calc
/CT
99.9
value of each
disinfection segment immediately prior to the next point of disinfectant
application, or for the final segment, before or at the first customer, during
peak hourly flow using the procedure specified in subsection (e)(1)(B).
f) Use of Chloramines,
Ozone, or Chlorine Dioxide as a Primary Disinfectant. If a supplier uses
chloramines, ozone, or chlorine dioxide for primary disinfection, the supplier must
also calculate the logs of inactivation for viruses and develop an additional
disinfection profile for viruses using methods approved by the Agency.
g) Development and Maintenance
of the Disinfection Profile in Graphic Form. Each log inactivation serves as a
data point in the supplier's disinfection profile. A supplier will have
obtained 52 measurements (one for every week of the year). This will allow the
supplier and the Agency the opportunity to evaluate how microbial inactivation
varied over the course of the year by looking at all 52 measurements (the
supplier's disinfection profile). The supplier must keep the disinfection
profile data in graphic form, such as a spreadsheet, which must be available
for review by the Agency as part of a sanitary survey. The supplier must use
this data to calculate a benchmark if the supplier is considering changes to
disinfection practices.
BOARD
NOTE: Derived from 40 CFR 141.530 through 141.536.