35 Ill. Adm. Code 6110.611.955
Combined Filter Effluent Turbidity Limits
TITLE 35: ENVIRONMENTAL PROTECTION
SUBTITLE F: PUBLIC WATER SUPPLIES
CHAPTER I: POLLUTION CONTROL BOARD
PART 611 PRIMARY DRINKING WATER STANDARDS
SECTION 611.955 COMBINED FILTER EFFLUENT TURBIDITY LIMITS
Section 611.955 Combined Filter
Effluent Turbidity Limits
a) Applicability. A
Subpart B system supplier that serves fewer than 10,000 persons, that is
required to filter, and that uses filtration other than slow sand filtration or
diatomaceous earth filtration must meet the combined filter effluent turbidity
requirements of subsections (b) through (d). If the supplier uses slow sand or
diatomaceous earth filtration the supplier is not required to meet the combined
filter effluent turbidity limits of this Subpart X, but the supplier must
continue to meet the combined filter effluent turbidity limits in Section
611.250.
b) Combined Filter Effluent
Turbidity Limits. A supplier must meet two strengthened combined filter
effluent turbidity limits.
1) The first combined
filter effluent turbidity limit is a "95
th
percentile"
turbidity limit that a supplier must meet in at least 95 percent of the
turbidity measurements taken each month. Measurements must continue to be
taken as described in Sections
611.531 and 611.533
. Monthly reporting must be
completed according to Section 611.957(a). The following are the required
limits for specific filtration technologies:
A) For a system with conventional
filtration or direct filtration, the 95
th
percentile turbidity value
is 0.3 NTU.
B) For a system with any
other alternative filter technology, the 95
th
percentile turbidity
value is a value (not to exceed 1 NTU) to be determined by the Agency, by a
SEP, based on the demonstration described in subsection (c).
2) The second combined
filter effluent turbidity limit is a "maximum" turbidity limit that a
supplier may at no time exceed during the month. Measurements must continue to
be taken as described in Sections
611.531 and 611.533
. Monthly reporting must be
completed according to Section 611.957(a). The following are the required
limits for specific filtration technologies:
A) For a system with
conventional filtration or direct filtration, the maximum turbidity value is 1
NTU.
B) For a system with any
other alternative filter technology, the maximum turbidity value is a value
(not to exceed 5 NTU) to be determined by the Agency, by a SEP, based on the
demonstration described in subsection (c).
c) Requirements for an Alternative
Filtration System
1) If a supplier's system
consists of alternative filtration (filtration other than slow sand filtration,
diatomaceous earth filtration, conventional filtration, or direct filtration) the
supplier is required to conduct a demonstration (see tables in subsection
(b)). The supplier must demonstrate to the Agency, using pilot plant studies
or other means, that its system's filtration, in combination with disinfection
treatment, consistently achieves the following:
A) 99 percent removal of
Cryptosporidium oocysts;
B) 99.9 percent removal or
inactivation of Giardia lamblia cysts; and
C) 99.99 percent removal or
inactivation of viruses.
2) This subsection (c)(2)
corresponds with 40 CFR 141.552(b), which USEPA has designated as "reserved".
This statement maintains structural correspondence with the corresponding
federal regulation.
d) Requirements for a Lime-Softening
System. If a supplier practices lime softening, the supplier may acidify
representative combined filter effluent turbidity samples prior to analysis
using a protocol approved by the Agency.
BOARD
NOTE: Derived from 40 CFR 141.550 through 141.553.