35 Ill. Adm. Code 6110.611.956
Individual Filter Turbidity Requirements
TITLE 35: ENVIRONMENTAL PROTECTION
SUBTITLE F: PUBLIC WATER SUPPLIES
CHAPTER I: POLLUTION CONTROL BOARD
PART 611 PRIMARY DRINKING WATER STANDARDS
SECTION 611.956 INDIVIDUAL FILTER TURBIDITY REQUIREMENTS
Section 611.956 Individual Filter
Turbidity Requirements
a) Applicability. A
Subpart B system supplier that serves fewer than 10,000 persons and utilizing
conventional filtration or direct filtration must conduct continuous monitoring
of turbidity for each individual filter in a supplier's system. The following
requirements apply to continuous turbidity monitoring:
1) Monitoring must be conducted
using an approved method in Section 611.531;
2) Calibration of
turbidimeters must be conducted using procedures specified by the manufacturer;
3) Results of turbidity
monitoring must be recorded at least every 15 minutes;
4) Monthly reporting must
be completed according to Section 611.957(a); and
5) Records must be
maintained according to Section 611.957(b).
b) Failure of Turbidity
Monitoring Equipment. If there is a failure in the continuous turbidity
monitoring equipment, the supplier must conduct grab sampling every four hours
in lieu of continuous monitoring until the turbidimeter is back on-line. The
supplier has 14 days to resume continuous monitoring before a violation is
incurred.
c) Special Requirements for
Systems with Two or Fewer Filters. If a supplier's system only consists of two
or fewer filters, the supplier may conduct continuous monitoring of combined
filter effluent turbidity in lieu of individual filter effluent turbidity
monitoring. Continuous monitoring must meet the same requirements in
subsections (a)(1) through (a)(4) and (b).
d) Follow-Up Action.
Follow-up action is required according to the following requirements:
1) If the turbidity of an
individual filter (or the turbidity of combined filter effluent (CFE) for a system
with two filters that monitor CFE in lieu of individual filters) exceeds 1.0
NTU in two consecutive recordings 15 minutes apart, the supplier must report to
the Agency by the 10
th
of the following month and include the filter
numbers, corresponding dates, turbidity values that exceeded 1.0 NTU, and the
cause (if known) for the
exceedances
.
2) If a supplier was
required to report to the Agency for three months in a row and turbidity
exceeded 1.0 NTU in two consecutive recordings 15 minutes apart at the same
filter (or CFE for systems with two filters that monitor CFE in lieu of
individual filters), the supplier must conduct a self-assessment of the filters
within 14 days after the day on which the filter exceeded 1.0 NTU in two
consecutive measurements for the third straight month, unless a CPE, as
specified in subsection (d)(3), was required. A supplier that has a system
with two filters that monitor CFE in lieu of individual filters must conduct a self-assessment
on both filters. The self-assessment must consist of at least the following
components: assessment of filter performance, development of a filter profile,
identification and prioritization of factors limiting filter performance,
assessment of the applicability of corrections, and preparation of a filter
self-assessment report.
3) If a supplier was
required to report to the Agency for two months in a row and turbidity exceeded
2.0 NTU in two consecutive recordings 15 minutes apart at the same filter (or
CFE for systems with two filters that monitor CFE in lieu of individual
filters), the supplier must arrange to have a comprehensive performance
evaluation (CPE) conducted by the Agency or a third party approved by the
Agency not later than 60 days following the day the filter exceeded 2.0 NTU in
two consecutive measurements for the second straight month. If a CPE has been
completed by the Agency or a third party approved by the Agency within the 12
prior months or the system and Agency are jointly participating in an ongoing
comprehensive technical assistance (CTA) project at the system, a new CPE is
not required. If conducted, a CPE must be completed and submitted to the
Agency no later than 120 days following the day the filter exceeded 2.0 NTU in
two consecutive measurements for the second straight month.
e) Special Individual
Filter Monitoring for a Lime-Softening System. If a supplier's system uses
lime softening, the supplier may apply to the Agency for alternative turbidity
exceedance
levels for the levels specified in
subsection (d). The supplier must be able to demonstrate to the Agency that
higher turbidity levels are due to lime carryover only, and not due to degraded
filter
performance.
BOARD
NOTE: Derived from 40 CFR 141.560 through 141.564.