35 Ill. Adm. Code 611.1017
Requirements for Microbial Toolbox Components: Pre-Filtration Treatment Toolbox Components
Section 611.1017Â Requirements for Microbial Toolbox
Components:Â Pre-Filtration Treatment Toolbox Components
a)Â Â Â Â Â Â Â Â Presedimentation.Â
A supplier receives 0.5-log Cryptosporidium treatment credit for a
presedimentation basin during any month the process meets the criteria in this
subsection (a).
1)Â Â Â Â Â Â Â Â The
presedimentation basin must be in continuous operation and must treat the
entire plant flow taken from a surface water or groundwater under the direct
influent of surface water source.
2)Â Â Â Â Â Â Â Â The
supplier must continuously add a coagulant to the presedimentation basin.
3)Â Â Â Â Â Â Â Â The
presedimentation basin must achieve both of the following performance criteria:
A)Â Â Â Â Â Â Â It
demonstrates at least 0.5-log mean reduction of influent turbidity. This
reduction must be determined using daily turbidity measurements in the
presedimentation process influent and effluent, and it must be calculated as
follows:Â log
10
(monthly mean of daily influent turbidity) - log
10
(monthly mean of daily effluent turbidity); and
B)Â Â Â Â Â Â Â It complies
with Agency-approved performance criteria that demonstrate at least 0.5-log
mean removal of micronsized particulate material through the presedimentation
process.
b)Â Â Â Â Â Â Â Â Two-Stage
Lime Softening. A supplier receives an additional 0.5-log Cryptosporidium
treatment credit for a two-stage lime softening plant if chemical addition and
hardness precipitation occur in two separate and sequential softening stages
prior to filtration. Both softening stages must treat the entire plant flow
taken from a surface water or groundwater under the direct influent of surface
water source.
c)Â Â Â Â Â Â Â Â Bank Filtration.Â
A supplier receives Cryptosporidium treatment credit for bank filtration that
serves as pretreatment to a filtration plant by meeting the criteria in this
subsection (c). A supplier using bank filtration when it begins source water
monitoring under Section 611.1001(a) must collect samples as described in
Section 611.1003(d), and it is not eligible for this credit.
1)Â Â Â Â Â Â Â Â A
well with a groundwater flow path of at least 25 feet receives 0.5-log
treatment credit, or a well with a groundwater flow path of at least 50 feet
receives 1.0-log treatment credit. The groundwater flow path must be
determined as specified in subsection (c)(4).
2)Â Â Â Â Â Â Â Â Only
a well in granular aquifers is eligible for treatment credit. A granular
aquifer is one comprised of sand, clay, silt, rock fragments, pebbles or larger
particles, and minor cement. A supplier must characterize the aquifer at the
well site to determine aquifer properties. A supplier must extract a core from
the aquifer and demonstrate that in at least 90 percent of the core length,
grains less than 1.0 mm in diameter constitute at least ten percent of the core
material.
3)Â Â Â Â Â Â Â Â Only
a horizontal or vertical well is eligible for treatment credit.
4)Â Â Â Â Â Â Â Â For a
vertical well, the groundwater flow path is the measured distance from the edge
of the surface water body under high flow conditions (determined by the 100
year floodplain elevation boundary or by the floodway, as defined in Federal
Emergency Management Agency flood hazard maps) to the well screen. For a
horizontal well, the groundwater flow path is the measured distance from the
bed of the river under normal flow conditions to the closest horizontal well
lateral screen.
5)Â Â Â Â Â Â Â Â The
supplier must monitor each wellhead for turbidity at least once every four
hours while the bank filtration process is in operation. If monthly average
turbidity levels, based on daily maximum values in the well, exceed 1 NTU, the
supplier must report this result to the Agency and conduct an assessment within
30 days to determine the cause of the high turbidity levels in the well. If
the Agency determines that microbial removal has been compromised, it may, by a
SEP, revoke treatment credit until the supplier implements corrective actions
approved by the Agency to remediate the problem.
6)Â Â Â Â Â Â Â Â Springs
and infiltration galleries are not eligible for treatment credit under this
Section, but are eligible for credit under Section 611.1018(c).
7)Â Â Â Â Â Â Â Â Bank Filtration
Demonstration of Performance. The Agency may, by a SEP, approve
Cryptosporidium treatment credit for bank filtration based on a demonstration
of performance study that meets the criteria in this subsection. This treatment
credit may be greater than 1.0-log and may be awarded to bank filtration that
does not meet the criteria in subsections (c)(1) through (c)(5).
A)Â Â Â Â Â Â Â The
study must follow an Agency-approved protocol and must involve the collection
of data on the removal of Cryptosporidium or a surrogate for Cryptosporidium
and related hydrogeologic and water quality parameters during the full range of
operating conditions.
B)Â Â Â Â Â Â Â The
study must include sampling both from the production wells and from monitoring
wells that are screened and located along the shortest flow path between the
surface water source and the production wells.
BOARD NOTE:Â Derived from 40 CFR
141.717.