35 Ill. Adm. Code 611.1018
Requirements for Microbial Toolbox Components: Treatment Performance Toolbox Components
Section 611.1018 Requirements for Microbial Toolbox
Components: Treatment Performance Toolbox Components
a) Combined
Filter Performance. A supplier that uses conventional filtration treatment or
direct filtration treatment receives an additional 0.5-log Cryptosporidium
treatment credit during any month it meets the criteria in this subsection
(a). Its combined filter effluent (CFE) turbidity must be less than or equal
to 0.15 NTU in at least 95 percent of the measurements. Turbidity must be
measured as described in Sections 611.531 and 611.533.
b) Individual
Filter Performance. A supplier that uses conventional filtration treatment or
direct filtration treatment receives 0.5-log Cryptosporidium treatment credit,
which can be in addition to the 0.5-log credit under subsection (a), during any
month it meets the criteria in this subsection (b). Compliance with these
criteria must be based on individual filter turbidity monitoring as described
in Section 611.744 or 611.956(a), as applicable.
1) The
filtered water turbidity for each individual filter must be less than or equal
to 0.15 NTU in at least 95 percent of the measurements recorded each month.
2) No
individual filter may have a measured turbidity greater than 0.3 NTU in two
consecutive measurements taken 15 minutes apart.
3) Any
supplier that has received treatment credit for individual filter performance
and fails to meet the requirements of subsection (b)(1) or (b)(2) during any
month does not receive a treatment technique violation under Section
611.1011(c) if the Agency determines the following:
A) The
failure was due to unusual and short-term circumstances that could not
reasonably be prevented through optimizing treatment plant design, operation,
and maintenance; and
B) The
supplier has experienced no more than two such failures in any calendar year.
c) Demonstration
of Performance. The Agency may, by a SEP, approve Cryptosporidium treatment
credit for drinking water treatment processes based on a demonstration of
performance study that meets the criteria in this subsection (c). This
treatment credit may be greater than or less than the prescribed treatment
credits in Section 611.1011 or Sections 611.1017 through 611.1020 and may be
awarded to treatment processes that do not meet the criteria for the prescribed
credits.
1) The
supplier cannot receive the prescribed treatment credit for any toolbox option
in Sections 611.1017 through 611.1020 if that toolbox option is included in a
demonstration of performance study for which treatment credit is awarded under
this subsection (b).
2) The
demonstration of performance study must follow an Agency-approved protocol and
must demonstrate the level of Cryptosporidium reduction the treatment process
will achieve under the full range of expected operating conditions for the
supplier.
3) Approval
by the Agency must be in writing and may include monitoring and treatment
performance criteria that the supplier must demonstrate and report on an
ongoing basis to remain eligible for the treatment credit. The Agency may, by
a SEP, designate such criteria where necessary to verify that the conditions
under which the demonstration of performance credit was approved are maintained
during routine operation.
BOARD NOTE: Derived from 40 CFR 141.718.