35 Ill. Adm. Code 611.1058
Repeat Monitoring and E. coli Requirements
Section 611.1058Â Repeat Monitoring and E. coli
Requirements
a)Â Â Â Â Â Â Â Â Repeat Monitoring
1)Â Â Â Â Â Â Â Â If a
sample taken under Sections 611.1054 through 611.1057 is total
coliform-positive, the supplier must collect a set of repeat samples within 24
hours after being notified of the positive result. The supplier must collect
no fewer than three repeat samples for each total coliform-positive sample
found. The Agency may, by a SEP, extend the 24-hour limit on a case-by-case
basis if the supplier has a logistical problem in collecting the repeat samples
within 24 hours that is beyond its control. Alternatively, the Agency may
implement criteria for the supplier to use in lieu of case-by-case extensions.Â
In the case of an extension, the Agency must specify how much time the supplier
has to collect the repeat samples. The Agency cannot waive the requirement for
a supplier to collect repeat samples in subsections (a)(1) through (a)(3).
2)Â Â Â Â Â Â Â Â The
supplier must collect all repeat samples on the same day, except that the
Agency may, by a SEP, allow a supplier with a single service connection to
collect the required set of repeat samples over a three-day period or to
collect a larger volume repeat samples in one or more sample containers of any
size, as long as the total volume collected is at least 300 mâ„“.
3)Â Â Â Â Â Â Â Â The
supplier must collect an additional set of repeat samples in the manner
specified in subsections (a)(1) through (a)(3) if one or more repeat samples in
the current set of repeat samples is total coliform-positive. The supplier must
collect the additional set of repeat samples within 24 hours after being
notified of the positive result, unless the Agency extends the limit as
provided in subsection (a)(1). The supplier must continue to collect
additional sets of repeat samples until either total coliforms are not detected
in one complete set of repeat samples or the supplier determines that a
coliform treatment technique trigger specified in Section 611.1059(a) has been
exceeded as a result of a repeat sample being total coliform-positive and
notifies the Agency. If a trigger identified in Section 611.1059 is exceeded
as a result of a routine sample being total coliform-positive, the supplier is
required to conduct only one round of repeat monitoring for each total
coliform-positive routine sample.
4)Â Â Â Â Â Â Â Â After
a supplier collects a routine sample and before it learns the results of the
analysis of that sample, if the supplier collects another routine sample from
within five adjacent service connections of the initial sample, and the initial
sample, after analysis, is found to contain total coliforms, then the system
may count the subsequent sample as a repeat sample instead of as a routine
sample.
5)Â Â Â Â Â Â Â Â Results
of all routine and repeat samples taken under Sections 611.1054 through
611.1058 not invalidated by the Agency must be used to determine whether a
coliform treatment technique trigger specified in Section 611.1059 has been
exceeded.
b)Â Â Â Â Â Â Â Â Escherichia coli (E.
coli) Testing
1)Â Â Â Â Â Â Â Â If
any routine or repeat sample is total coliform-positive, the supplier must
analyze that total coliform-positive culture medium to determine if E. coli are
present. If E. coli are present, the supplier must notify the Agency by the
end of the day when the supplier is notified of the test result, unless the
supplier is notified of the result after the Agency office is closed and the
Agency does not have either an after-hours phone line or an alternative
notification procedure, in which case the supplier must notify the Agency
before the end of the next business day.
2)Â Â Â Â Â Â Â Â The
Agency has the discretion to allow a supplier, on a case-by-case basis, to
forego E. coli testing on a total coliform-positive sample if that supplier
assumes that the total coliform-positive sample is E. coli-positive. Accordingly,
the supplier must notify the Agency as specified in subsection (b)(1) and the
provisions of Section 141.63(c) apply.
BOARD NOTE:Â Derived from 40 CFR
141.858.