35 Ill. Adm. Code 724.296
Response to Leaks or Spills and Disposition of Leaking or Unfit-for-Use Tank Systems
Section 724
Section 724.296Â Response to
Leaks or Spills and Disposition of Leaking or Unfit-for-Use Tank Systems
A tank system or secondary
containment system from which there has been a leak or spill, or which is unfit
for use, must be removed from service immediately, and the owner or operator must
satisfy the following requirements:
a)        Cease Using; Prevent Flow or Addition of Wastes. The owner or
operator must immediately stop the flow of hazardous waste into the tank system
or secondary containment system and inspect the system to determine the cause
of the release.
b)Â Â Â Â Â Â Â Â Removal of Waste from Tank System or Secondary Containment
System
1)Â Â Â Â Â Â Â Â If the release was from the tank system, the owner or operator
must, within 24 hours after detection of the leak or as otherwise provided in
the permit, remove as much of the waste as is necessary to prevent further
release of hazardous waste to the environment and to allow inspection and
repair of the tank system to be performed.
2)Â Â Â Â Â Â Â Â If the material released was to a secondary containment
system, all released materials must be removed within 24 hours or as otherwise
provided in the permit to prevent harm to human health and the environment.
c)        Containment of Visible Releases to the Environment. The owner
or operator must immediately conduct a visual inspection of the release and,
based upon that inspection, do the following:
1)Â Â Â Â Â Â Â Â Prevent further migration of the leak or spill to soils or
surface water; and
2)Â Â Â Â Â Â Â Â Remove and properly dispose of any visible contamination of
the soil or surface water.
d)Â Â Â Â Â Â Â Â Notifications, Reports
1)Â Â Â Â Â Â Â Â Any release to the environment, except as provided in
subsection (d)(2), must be reported to the Agency within 24 hours of its
detection.
2)Â Â Â Â Â Â Â Â A leak or spill of hazardous waste is exempted from the
requirements of this subsection (d) if the following is true:
A)       The spill was less than or equal to a quantity of one pound (0.45
kg); and
B)Â Â Â Â Â Â Â It was immediately contained and cleaned up.
3)Â Â Â Â Â Â Â Â Within 30 days of detection of a release to the environment, a
report containing the following information must be submitted to the Agency:
A)Â Â Â Â Â Â Â Likely route of migration of the release;
B)Â Â Â Â Â Â Â Characteristics of the surrounding soil (soil composition,
geology, hydrogeology, climate, etc.);
C)Â Â Â Â Â Â Â Results of any monitoring or sampling conducted in connection
with the release (if available). If sampling or monitoring data relating to
the release are not available within 30 days, these data must be submitted to
the Agency as soon as they become available.
D)Â Â Â Â Â Â Â Proximity the downgradient drinking water, surface water, and
populated areas; and
E)Â Â Â Â Â Â Â Description of response actions taken or planned.
e)Â Â Â Â Â Â Â Â Provision of Secondary Containment, Repair, or Closure
1)Â Â Â Â Â Â Â Â Unless the owner or operator satisfies the requirements of
subsections (e)(2) through (e)(4), the tank system must be closed in accordance
with Section 724.297.
2)Â Â Â Â Â Â Â Â If the cause of the release was a spill that has not damaged
the integrity of the system, the owner or operator may return the system to
service as soon as the released waste is removed and repairs, if necessary, are
made.
3)Â Â Â Â Â Â Â Â If the cause of the release was a leak from the primary tank
system into the secondary containment system, the system must be repaired prior
to returning the tank system to service.
4)Â Â Â Â Â Â Â Â If the source of the release was a leak to the environment
from a component of a tank system without secondary containment, the owner or
operator must provide the component of the system from which the leak occurred
with secondary containment that satisfies the requirements of Section 724.293
before it can be returned to service, unless the source of the leak is an
aboveground portion of a tank system that can be inspected visually. If the
source is an aboveground component that can be inspected visually, the
component must be repaired and may be returned to service without secondary
containment, as long as the requirements of subsection (f) are satisfied. If a
component is replaced to comply with the requirements of this subsection (e),
that component must satisfy the requirements of new tank systems or components
in Sections 724.292 and 724.293. Additionally, if a leak has occurred in any
portion of a tank system component that is not readily accessible for visual
inspection (e.g., the bottom of an in-ground or on-ground tank), the entire
component must be provided with secondary containment in accordance with
Section 724.293 prior to being returned to use.
f)        Certification of Major Repairs. If the owner or operator has
repaired a tank system in accordance with subsection (e), and the repair has
been extensive (e.g., installation of an internal liner, repair, or a ruptured
primary containment or secondary containment vessel), the tank system must not
be returned to service unless the owner or operator has obtained a
certification by a qualified Professional Engineer, in accordance with 35 Ill.
Adm. Code 702.126(d), that the repaired system is capable of handling hazardous
wastes without release for the intended life of the system. This certification
must be placed in the operating record and maintained until closure of the
facility.
BOARD NOTE:Â
See Section 724.115(c) for the requirements necessary to remedy a failure.Â
Also, federal 40 CFR 302.6 may require the owner or operator to notify the
National Response Center of any "reportable quantity".