35 Ill. Adm. Code 724.956
Standards: Open-Ended Valves or Lines
Section 724
Section 724.956 Standards: Open-Ended
Valves or Lines
a) Equipment
1) Each open-ended valve or line must be equipped with a cap,
blind flange, plug, or a second valve.
2) The cap, blind flange, plug, or second valve must seal the
open end at all times except during operations requiring hazardous wastestream
flow through the open-ended valve or line.
b) Each open-ended valve or line equipped with a second valve
must be operated in a manner such that the valve on the hazardous wastestream
end is closed before the second valve is closed.
c) When a double block and bleed system is being used, the bleed
valve or line may remain open during operations that require venting the line
between the block valves but must comply with subsection (a) at all other
times.