35 Ill. Adm. Code 724.957
Standards: Valves in Gas/Vapor or Light Liquid Service
Section 724
Section 724.957Â Standards:Â
Valves in Gas/Vapor or Light Liquid Service
a)Â Â Â Â Â Â Â Â Each valve in gas-vapor or light liquid service must be
monitored monthly to detect leaks by the methods specified in Section
724.963(b) and must comply with subsections (b) through (e), except as provided
in subsections (f), (g), and (h), and in Sections 724.961 and 724.962.
b)Â Â Â Â Â Â Â Â If an instrument reading of 10,000 ppm or greater is measured,
a leak is detected.
c)Â Â Â Â Â Â Â Â Monitoring Frequency
1)Â Â Â Â Â Â Â Â Any valve for which a leak is not detected for two successive
months must be monitored the first month of every succeeding quarter, beginning
with the next quarter, until a leak is detected.
2)Â Â Â Â Â Â Â Â If a leak is detected, the valve must be monitored monthly
until a leak is not detected for two successive months.
d)Â Â Â Â Â Â Â Â Leak Repair
1)Â Â Â Â Â Â Â Â When a leak is detected, it must be repaired as soon as
practicable, but no later than 15 calendar days after the leak is detected,
except as provided in Section 724.959.
2)Â Â Â Â Â Â Â Â A first attempt at repair must be made no later than five calendar
days after each leak is detected.
e)Â Â Â Â Â Â Â Â First attempts at repair include, but are not limited to the
following best practices where practicable:
1)Â Â Â Â Â Â Â Â Tightening bonnet bolts.
2)Â Â Â Â Â Â Â Â Replacing bonnet bolts.
3)Â Â Â Â Â Â Â Â Tightening packing gland nuts.
4)Â Â Â Â Â Â Â Â Injecting lubricant into lubricated packing.
f)Â Â Â Â Â Â Â Â Any valve that is designated, as described in Section
724.964(g)(2), for no detectable emissions, as indicated by an instrument
reading of less than 500 ppm above background, is exempt from the requirements
of subsection (a) if the following is true of the valve:
1)Â Â Â Â Â Â Â Â It has no external actuating mechanism in contact with the
hazardous wastestream.
2)Â Â Â Â Â Â Â Â It is operated with emissions less than 500 ppm above
background as determined by the method specified in Section 724.963(c).
3)Â Â Â Â Â Â Â Â It is tested for compliance with subsection (f)(2) initially
upon designation, annually, and at other times as specified in the RCRA permit.
g)Â Â Â Â Â Â Â Â Any valve that is designated, as described in Section
724.964(h)(1), as an unsafe-to-monitor valve is exempt from the requirements of
subsection (a), if the following occurs:
1)Â Â Â Â Â Â Â Â The owner or operator of the valve determines that the valve
is unsafe to monitor because monitoring personnel would be exposed to an
immediate danger as a consequence of complying with subsection (a).
2)Â Â Â Â Â Â Â Â The owner or operator of the valve adheres to a written plan
that requires monitoring of the valve as frequently as practicable during
safe-to-monitor times.
h)Â Â Â Â Â Â Â Â Any valve that is designated, as described in Section
724.964(h)(2), as a difficult-to-monitor valve is exempt from the requirements
of subsection (a), if the following occurs:
1)Â Â Â Â Â Â Â Â The owner or operator of the valve determines that the valve
cannot be monitored without elevating the monitoring personnel more than two
meters above a support surface;
2)Â Â Â Â Â Â Â Â The hazardous waste management unit within which the valve is
located was in operation before June 21, 1990; and
3)Â Â Â Â Â Â Â Â The owner or operator of the valve follows a written plan that
requires monitoring of the valve at least once per calendar year.