35 Ill. Adm. Code 724.961
Alternative Percentage Standard for Valves
Section 724
Section 724.961Â Alternative
Percentage Standard for Valves
a)Â Â Â Â Â Â Â Â An owner or operator subject to the requirements of Section
724.957 may elect to have all valves within a hazardous waste management unit
comply with an alternative standard that allows no greater than two percent of
the valves to leak.
b)Â Â Â Â Â Â Â Â The following requirements must be met if an owner or operator
decides to comply with the alternative standard of allowing two percent of
valves to leak:
1)Â Â Â Â Â Â Â Â A performance test as specified in subsection (c) must be
conducted initially upon designation, annually and other times specified in the
RCRA permit.
2)Â Â Â Â Â Â Â Â If a valve leak is detected it must be repaired in accordance
with Section 724.957(d) and (e).
c)Â Â Â Â Â Â Â Â Performance tests must be conducted in the following manner:
1)Â Â Â Â Â Â Â Â All valves subject to the requirements in Section 724.957
within the hazardous waste management unit must be monitored within one week by
the methods specified in Section 724.963(b).
2)Â Â Â Â Â Â Â Â If an instrument reading of 10,000 ppm or greater is measured,
a leak is detected.
3)Â Â Â Â Â Â Â Â The leak percentage must be determined by dividing the number
of valves subject to the requirements in Section 724.957 for which leaks are
detected by the total number of valves subject to the requirements in Section
724.957 within the hazardous waste management unit.