35 Ill. Adm. Code 739.164
Used Oil Storage
Section 739
Section 739.164Â Used Oil
Storage
A used oil burner is subject to
all applicable Spill Prevention, Control and Countermeasures (federal 40 CFR
112) in addition to the requirements of this Subpart G. Â A used oil burner is
also subject to the Underground Storage Tank (35 Ill. Adm. Code 731) standards
for used oil stored in underground tanks whether or not the used oil exhibits
any characteristics of hazardous waste, in addition to the requirements of this
Subpart G.
a)        Storage Units. A used oil burner may not store used oil in
units other than tanks, containers, or units subject to regulation under 35
Ill. Adm. Code 724 or 725.
b)        Condition of Units. The following must be true of containers
and aboveground tanks used to store used oil at a burner facility:
1)Â Â Â Â Â Â Â Â The containers must be in good condition (no severe rusting,
apparent structural defects or deterioration); and
2)Â Â Â Â Â Â Â Â The containers may not be leaking (no visible leaks).
c)        Secondary Containment for Containers. Containers used to
store used oil at a burner facility must be equipped with a secondary
containment system.
1)Â Â Â Â Â Â Â Â The secondary containment system must consist of the following,
at a minimum:
A)Â Â Â Â Â Â Â Dikes, berms, or retaining walls; and
B)       A floor. The floor must cover the entire area within the dike,
berm, or retaining wall.
2)Â Â Â Â Â Â Â Â The entire containment system, including walls and floor, must
be sufficiently impervious to used oil to prevent any used oil released into
the containment system from migrating out of the system to the soil,
groundwater, or surface water.
d)Â Â Â Â Â Â Â Â Secondary Containment for Existing Aboveground Tanks.Â
Existing aboveground tanks used to store used oil at burner facilities must be
equipped with a secondary containment system.
1)Â Â Â Â Â Â Â Â The secondary containment system must consist of the following,
at a minimum:
A)Â Â Â Â Â Â Â Both of the following:
i)Â Â Â Â Â Â Â Â Â Dikes, berms, or retaining walls; and
ii)        A floor. The floor must cover the entire area within the
dike, berm, or retaining wall except areas where existing portions of the tank
meet the ground; or
B)Â Â Â Â Â Â Â An equivalent secondary containment system.
2)Â Â Â Â Â Â Â Â The entire containment system, including walls and floor, must
be sufficiently impervious to used oil to prevent any used oil released into
the containment system from migrating out of the system to the soil,
groundwater, or surface water.
e)        Secondary Containment for New Aboveground Tanks. A new
aboveground tank used to store used oil at burner facilities must be equipped
with a secondary containment system.
1)Â Â Â Â Â Â Â Â The secondary containment system must consist of the following,
at a minimum:
A)Â Â Â Â Â Â Â Both of the following:
i)Â Â Â Â Â Â Â Â Â Dikes, berms, or retaining walls; and
ii)        A floor. The floor must cover the entire area within the
dike, berm, or retaining wall; or
B)Â Â Â Â Â Â Â An equivalent secondary containment system.
2)Â Â Â Â Â Â Â Â The entire containment system, including walls and floor, must
be sufficiently impervious to used oil to prevent any used oil released into
the containment system from migrating out of the system to the soil,
groundwater, or surface water.
f)Â Â Â Â Â Â Â Â Labels
1)Â Â Â Â Â Â Â Â A container or aboveground tank used to store used oil at a burner
facility must be labeled or marked clearly with the words "Used Oil".
2)Â Â Â Â Â Â Â Â Fill pipes used to transfer used oil into underground storage
tanks at burner facilities must be labeled or marked clearly with the words
"Used Oil".
g)        Response to Releases. Upon detection of a release of used oil
to the environment that is not subject to the federal requirements of subpart F
of 40 CFR 280 and which has occurred after October 4, 1996, a burner must
perform the following cleanup steps:
BOARD NOTE:Â
Corresponding 40 CFR 279.64(g) applies to releases that "occurred after
the effective date of the authorized used oil program for the State in which
the release is located". The Board adopted the used oil standards in
docket R93-4 at 17 Ill. Reg. 20954, effective November 22, 1993. USEPA approved
the Illinois standards at 61 Fed. Reg. 40521 (Aug. 5, 1996), effective October
4, 1996. The Board has interpreted "the effective date of the authorized
used oil program" to mean the October 4, 1996 date of federal
authorization of the Illinois program, and we substituted that date for the
federal effective date language. Had USEPA written something like "the
effective date of the used oil program in the authorized State in which the
release is located", the Board would have used the November 22, 1993
effective date of the Illinois used oil standards.
1)Â Â Â Â Â Â Â Â Stop the release;
2)Â Â Â Â Â Â Â Â Contain the released used oil;
3)Â Â Â Â Â Â Â Â Properly clean up and manage the released used oil and other
materials; and
4)Â Â Â Â Â Â Â Â If necessary, repair or replace any leaking used oil storage
containers or tanks prior to returning them to service.