35 Ill. Adm. Code 811.308
Leachate Collection System
Section 811
Section 811.308 Leachate
Collection System
a) The leachate collection system shall be designed and
constructed to function for the entire design period.
b) Collection pipes shall be designed for open channel flow to
convey leachate under the conditions established in Section 811.307(b).
c) Collection pipes shall be of a cross sectional area that
allows cleaning.
d) Materials used in the leachate collection system shall be
chemically resistant to the leachate expected to be produced.
e) The collection pipe material and bedding materials as placed
shall possess structural strength to support the maximum loads imposed by the
overlying materials and equipment used at the facility.
f) Collection pipes shall be constructed within a coarse gravel
envelope using a graded filter or geotextile as necessary to minimize clogging.
g) The system shall be equipped with a sufficient number of
manholes and cleanout risers to allow cleaning and maintenance of all pipes
throughout the design period.
h) Leachate shall be able to drain freely from the collection
pipes. If sumps are used then pumps shall remove the collected leachate before
the level of leachate in the sumps rise above the invert of the collection
pipes under the conditions established in Section 811.307(b).