35 Ill. Adm. Code 811.310
Landfill Gas Monitoring
Section 811
Section 811.310 Landfill Gas
Monitoring
a) This Section applies to all units that dispose putrescible
wastes.
b) Location and Design of Monitoring Wells
1) Gas monitoring devices must be placed at intervals and
elevations within the waste to provide a representative sampling of the
composition and buildup of gases within the unit.
2) Gas monitoring devices must be placed around the unit at
locations and elevations capable of detecting migrating gas from the ground
surface to the lowest elevation of the liner system or the top elevation of the
groundwater, whichever is higher.
3) A predictive gas flow model may be utilized to determine the
optimum placement of monitoring points required for making observations and
tracing the movement of gas.
4) Gas monitoring devices must be constructed from materials that
will not react with or be corroded by the landfill gas.
5) Gas monitoring devices must be designed and constructed to
measure pressure and allow collection of a representative sample of gas.
6) Gas monitoring devices must be constructed and maintained to
minimize gas leakage.
7) The gas monitoring system must not interfere with the
operation of the liner, leachate collection system, or delay the construction
of the final cover system.
8) At least three ambient air monitoring locations must be chosen
and samples must be taken no higher than 0.025 meter (1 inch) above the ground
and 30.49m (100 feet) downwind from the edge of the unit or at the property
boundary, whichever is closer to the unit.
c) Monitoring Frequency
1) All gas monitoring devices, including the ambient air monitors
must be operated to obtain samples on a monthly basis for the entire operating
period and for a minimum of five years after closure.
2) After a minimum of five years after closure, monitoring
frequency may be reduced to quarterly sampling intervals.
3) The sampling frequency may be reduced to yearly sampling
intervals upon the installation and operation of a gas collection system
equipped with a mechanical device such as a compressor to withdraw gas.
4) Monitoring must be continued for a minimum period of: 30
years after closure at MSWLF units, except as otherwise provided by subsections
(c)(5) and (c)(6); five years after closure at landfills, other than MSWLF
units, which are used exclusively for disposing of wastes generated at the
site; or 15 years after closure at all other landfills regulated under this
Part. Monitoring, beyond the minimum period, may be discontinued if the
following conditions have been met for at least one year:
A) The concentration of methane is less than five percent of the
lower explosive limit in air for four consecutive quarters at all monitoring
points outside the unit; and
B) Monitoring points within the unit indicate that methane is no
longer being produced in quantities that would result in migration from the
unit and exceed the standards of subsection (a)(1).
5) The Agency may reduce the gas monitoring period at an MSWLF
unit upon a demonstration by the owner or operator that the reduced period is
sufficient to protect human health and environment.
6) The owner or operator of an MSWLF unit must petition the Board
for an adjusted standard in accordance with Section 811.303, if the owner or
operator seeks a reduction of the postclosure care monitoring period for all of
the following requirements:
A) Inspection and maintenance (Section 811.111);
B) Leachate collection (Section 811.309);
C) Gas monitoring (Section 811.310); and
D) Groundwater monitoring (Section 811.319).
BOARD NOTE: Those
segments of this subsection (c) that relate to MSWLF units are derived from 40
CFR 258.61 (2017).
d) Parameters to be Monitored
1) All below ground monitoring devices must be monitored for the
following parameters at each sampling interval:
A) Methane;
B) Pressure;
C) Oxygen; and
D) Carbon dioxide.
2) Ambient air monitors must be sampled for methane only when the
average wind velocity is less than eight kilometers (five miles) per hour at a
minimum of three downwind locations 30.49 meters (100 feet) from the edge of
the unit or the property boundary, whichever is closer to the unit.
3) All buildings within a facility must be monitored for methane
by utilizing continuous detection devices located at likely points where
methane might enter the building.
e) Any alternative frequencies for the monitoring requirement of
subsection (c) for any owner or operator of an MSWLF that disposes of 20 tons (18
megagrams) of municipal solid waste per day or less, based on an annual
average, must be established by an adjusted standard pursuant to Section 28.1
of the Act and Subpart D of 35 Ill. Adm. Code 104. Any alternative monitoring
frequencies established under this subsection (e) must fulfill the following
requirements:
1) They must consider the unique characteristics of small
communities;
2) They must take into account climatic and hydrogeologic
conditions; and
3) They must be protective of human health and the environment.
BOARD NOTE: This
subsection (e) is derived from 40 CFR 258.23(e) (2017).