35 Ill. Adm. Code 845.420
Leachate Collection and Removal System
Section
845.420 Leachate Collection and Removal System
A new CCR surface impoundment must be designed, constructed,
operated and maintained with a leachate collection and removal system. The
leachate collection and removal system must be designed, constructed, operated,
and maintained to collect and remove leachate from the leachate collection
system of the CCR surface impoundment during its active life and post-closure
care period.
a) The leachate collection
and removal system must:
1) Be placed above the
liner required by Section 845.400 or Section 845.410;
2) Have
placed above it a filter layer that has a hydraulic conductivity of at least 1 x
10
-5
cm/sec;
3) Have a
bottom slope of three percent or more towards the collection pipes;
4) Be
constructed of:
A) Granular
drainage materials with a hydraulic conductivity of 1 x 10
‑1
cm/sec or more and a thickness of 24 inches or more above the crown of the
collection pipe; or
B) Synthetic
drainage materials with a transmissivity of 6 x 10
-4
m
2
/sec
or more;
5) Be
constructed of materials that are chemically resistant to CCR and any non-CCR
waste managed in the CCR surface impoundment and the leachate expected to be
generated, and of sufficient strength and thickness to prevent collapse under
the pressures exerted by overlying waste and any waste cover materials and
equipment used at the CCR surface impoundment;
6) Be
designed, constructed and operated with collection pipes at the base of the
granular material to prevent clogging with fines during the active life and
post-closure care period;
7) Have
collection pipes:
A) Designed
such that leachate is collected at a sump and is pumped or flows out of the CCR
surface impoundment;
B) With
slopes that allow flow from all points within the CCR surface impoundment to
the sump or drain outlet; and
C) Large
enough to conduct periodic cleaning;
8) Have
a protective layer or other means of deflecting the force of CCR pumped into
the CCR surface impoundment;
9) Be
designed and operated to minimize clogging during the active life and
post-closure care period; and
10) At
a minimum, the leachate collection and removal system must be operated to
remove free liquids from the CCR surface impoundment at the time of closure and
during post closure care.
b) The
owner or operator must obtain certification from a qualified professional
engineer that the design of the leachate collection system complies with the
requirements of this Section and submit this certification to the Agency in the
facility's construction permit application.
c) Upon completion, the owner or operator must
obtain a certification from a qualified professional engineer that the leachate
collection system has been constructed in accordance with the requirements of
this Section and submit this certification to the Agency in the facility's
initial operating permit application.