77 Ill. Adm. Code 250.2490
Plumbing and Other Piping Systems
Section 250
Section 250.2490Â Plumbing
and Other Piping Systems
a)Â Â Â Â Â Â Â Â General
All plumbing systems shall be designed and installed in
accordance with the requirements of the Illinois Plumbing Code, except that the
number of waterclosets, urinals, lavatories, bathtubs, showers, drinking
fountains, and other fixtures shall be as required by this Part and the
hospital programs.
b)Â Â Â Â Â Â Â Â Plumbing Fixtures
1)Â Â Â Â Â Â Â Â Plumbing fixtures shall be of nonabsorptive acid-resistant
materials.
2)Â Â Â Â Â Â Â Â The water supply spout for lavatories and sinks required for
filling pitchers and for medical and nursing staff and food handlers'
hand-washing, shall be mounted so that its discharge point has a minimum
perpendicular distance of 5 inches above the rim of the fixture.
3)Â Â Â Â Â Â Â Â Hand-washing lavatories used by medical and nursing staff and
food handlers shall be trimmed with valves that can be operated without the use
of hands where specifically required in this Part.
A)Â Â Â Â Â Â Â When blade handles are used, the blade handles shall not exceed
4½ inches in length, except that the handles on clinical sinks shall not be
less than 6 inches in length.
B)Â Â Â Â Â Â Â The hand-washing and/or scrub sinks, for operating, emergency
treatment, nursery, and delivery rooms shall be trimmed with valves that are aseptically
operated (i.e., knee or foot controls) without the use of hands. Wrist blades
are not acceptable.
4)Â Â Â Â Â Â Â Â Clinical rim flush sinks shall have an integral trap in which
the upper portion of a visible trap seal provides a water surface.
5)Â Â Â Â Â Â Â Â Shower bases and tubs shall be provided with nonslip surfaces.
c)Â Â Â Â Â Â Â Â Water Supply Systems
1)Â Â Â Â Â Â Â Â Systems shall be designed to supply water at sufficient
pressure to operate all fixtures and equipment during maximum demand periods.
2)Â Â Â Â Â Â Â Â Each water service main, branch main, riser and branch to a
group of fixtures shall be valved. Stop valves shall be provided at each
fixture.
3)Â Â Â Â Â Â Â Â Flush valves installed on plumbing fixtures shall be of a
quiet operating type, equipped with silencers.
4)Â Â Â Â Â Â Â Â Bedpan-flushing devices shall be provided on each patient
toilet unless a clinical service sink is centrally located in each nursing
unit. This requirement does not apply to psychiatric units.
5)Â Â Â Â Â Â Â Â Water distribution systems shall be arranged to provide hot
water at each hot water outlet at all times. Hot water at shower, bathing, and
hand-washing facilities shall not exceed 110º F (43º C). If the program
requires, in psychiatric units, plumbing fixtures that require hot water and
are accessible to patients shall be supplied with hot water not to exceed 100º
F (38º C).
d)Â Â Â Â Â Â Â Â Hot Water Heaters and Tanks
1)Â Â Â Â Â Â Â Â The hot water heating equipment shall have sufficient capacity
to supply water at the temperatures and quantities in the following areas:
Clinical
Dietary
Laundry
gallons/hour/bed
6½
4
4½
liters/second/bed
.007
.004
.005
temperature ºF
100
180
180
temperature ºC
43
82
82
Water
temperatures are to be taken at the hot water point of use or at the inlet to the
processing equipment.
2)Â Â Â Â Â Â Â Â Storage tanks shall be fabricated of corrosion-resistant metal
or lined with non-corrosive material.
e)Â Â Â Â Â Â Â Â Drainage Systems
1)Â Â Â Â Â Â Â Â Drain lines from sinks in which acid wastes may be poured
shall be constructed of acid-resistant material.
2)Â Â Â Â Â Â Â Â Insofar as possible, drain piping shall not be installed over
operating and delivery rooms; nurseries; food preparation, serving, and storage
areas; and similar critical areas. Special precautions shall be taken to
protect these areas from possible leakage or condensation from overhead piping
systems.
3)Â Â Â Â Â Â Â Â Floor drains shall not be installed in operating rooms.Â
Flushing rim type drains may be installed in cytoscopic operating rooms.
4)Â Â Â Â Â Â Â Â Building sewers shall discharge into a public sewer system.
5)Â Â Â Â Â Â Â Â When a public sewer system is not available, plans for any
private sewage disposal system shall be submitted to the Environmental
Protection Agency for review for approval before hospital construction is
started.
f)Â Â Â Â Â Â Â Â Nonflammable medical gas systems shall be installed in
accordance with NFPA 99, Standard for Health Care Facilities.
g)Â Â Â Â Â Â Â Â Clinical vacuum (suction) systems shall be installed in
accordance with NFPA 99, Standard for Health Care Facilities.
h)Â Â Â Â Â Â Â Â Medical compressed air systems shall be installed in
accordance with NFPA 99, Standard for Health Care Facilities.
i)Â Â Â Â Â Â Â Â Â Oxygen, vacuum, and medical compressed air shall be piped to
the locations indicated in Table E with the required station outlets.
j)Â Â Â Â Â Â Â Â Â Service outlets for central housekeeping vacuum systems, if
used, shall not be located within operating rooms.
k)Â Â Â Â Â Â Â Â Fire Extinguishing Systems
1)Â Â Â Â Â Â Â Â All fire extinguishing systems shall be designed, installed,
and maintained in accordance with NFPA 101, Life Safety Code, NFPA Â 13,
Standards for the Installation of Sprinkler Systems, and NFPA 25A, Standard for
the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems.
2)Â Â Â Â Â Â Â Â Class III, Type 1 inside standpipe systems shall be provided
in all buildings more than four stories or 55 feet in height. Such standpipe
systems shall comply with NFPA 14, Standard for the Installation of Standpipe,
Private Hydrants and Hose Systems.