77 Ill. Adm. Code 250.2660
Mechanical
Section 250
Section 250.2660Â Mechanical
a)Â Â Â Â Â Â Â Â Any retrofit of existing heating, ventilating, or air
conditioning systems for energy conservation purposes may meet any or all of
the requirements of Section 250.2480 (Mechanical) in lieu of the parallel
requirements of this Section.
b)Â Â Â Â Â Â Â Â Boiler feed pumps, return pumps, and circulating pumps shall
be furnished in duplicate, each of which has a capacity to carry the full load.
Blow off valves, relief valves, nonreturn valves, injectors and fittings shall
be provided to meet the requirements of the city and state codes and
recommendations of the American Society of Mechanical Engineers.
c)Â Â Â Â Â Â Â Â Air Conditioning, Heating and Ventilating Systems
1)Â Â Â Â Â Â Â Â The systems should be capable of providing the following
temperatures and humidities in the following areas:
Temperature
Relative
Humidity %
Area
Designation
ºF
ºC
Min.
Max.
Operating Room
70-76*
21-24*
50
60
Delivery Room
70-76*
21-24*
50
60
Recovery Room
75
24
50
60
Intensive Care Units
75-80*
24-27*
30
60
Nursing Units
75
24
30
60
Special Care Nusery Units
75-80*
24-27*
30
60
Other patient areas
75
24
*Variable range required
2)Â Â Â Â Â Â Â Â Ventilation Systems
A)Â Â Â Â Â Â Â Air handling systems shall conform to NFPA 90A, Standard for
Installation of Air Conditioning and Ventilating Systems.
B)Â Â Â Â Â Â Â Outdoor intakes shall be located as far as practical but not
less than 15 feet from exhaust outlets of ventilation systems, combustion
equipment stacks, medical-surgical vacuum systems, plumbing vent stacks, or
from areas that may collect vehicular exhaust and other noxious fumes.
C)Â Â Â Â Â Â Â All ventilation air supplied to operating rooms, delivery rooms
and nurseries shall be delivered at or near the ceiling of the area served, and
all exhaust air from the area shall be removed near the floor level. At least
two exhaust outlets shall be used in all operating and delivery rooms.
D)Â Â Â Â Â Â Â All central ventilation or air conditioning systems shall be
equipped with filters having efficiencies no less than those specified in the
following:
FILTER EFFICIENCIES FOR CENTRAL VENTILATION AND AIR
CONDITIONING SYSTEMS IN GENERAL HOSPITALS
Area
Designation
Filter
Efficiencies (percent)
Sensitive Areas*
50
Patient Care, Treatment, Diagnostic and Related Areas
50
Food Preparation Areas and
Laundries
50
Administrative, Bulk Storage and Soiled Holding Areas
20
*Includes operating rooms, delivery rooms, nurseries, recovery rooms,
and intensive care units.
E)Â Â Â Â Â Â Â The filter shall be located upstream of the air conditioning
equipment. If a prefilter is installed, it shall be located upstream of the air
conditioning equipment. The main filter may be located before or after the
equipment.
F)Â Â Â Â Â Â Â Â Access to filters for changing shall be provided outside of
clean areas unless approved otherwise by the Department.
G)Â Â Â Â Â Â Â All filter efficiencies shall be average atmospheric dust spot
efficiencies tested in accordance with the ASHRAE Handbook of Fundamentals.
H)Â Â Â Â Â Â Â Filter frames shall be durable and shall provide an airtight
fit with the enclosing duct work. All joints between filter segments and
enclosing duct work shall be gasketed or sealed to provide a positive seal
against air leakage.
I)Â Â Â Â Â Â Â Â A manometer shall be installed across each filter bed serving
central air systems.
J)Â Â Â Â Â Â Â Â Ducts that penetrate construction intended for X-ray or other
ray protection shall maintain the effectiveness of the protection.
K)Â Â Â Â Â Â Â Fire and smoke dampers shall be constructed, located and
installed in accordance with the requirements of NFPA 90A, Standard for
Installation of Air Conditioning and Ventilating Systems. Exception: all
systems, regardless of size, that serve more than one smoke or fire zone, shall
be equipped with smoke detectors to shut down fans automatically as specified
in Paragraph 4-3.1 of NFPA 90A.
L)Â Â Â Â Â Â Â Laboratory hoods shall meet the following general requirements:
i)Â Â Â Â Â Â Â Â Â The exhaust system shall be separate from the building
exhaust system; and
ii)Â Â Â Â Â Â Â Â The exhaust duct system shall be of noncombustible
corrosion-resistant material consistent with the usage of the hood.
M)Â Â Â Â Â Â Laboratory hoods shall meet the following special requirements:
i)Â Â Â Â Â Â Â Â Â Each hood for the processing of infectious or radioactive
materials shall have an adequate face velocity, shall be connected to an
independent exhaust system, shall be provided with filters with 99.97 percent
efficiency (based on the DOD, diocytlphthalate test method as described in DOD
Penetration Test Method MIL STD 282:Â Filter Units, Protective Clothing,
Gas-Mask Components and Related Products:Â Performance Test Methods) in the
exhaust system, and shall be designed and equipped to permit the safe removal,
disposal and replacement of contaminated filters.
ii)Â Â Â Â Â Â Â Â Duct systems in which radioactive and strong oxidizing agents
are present shall be constructed of corrosion‑resistant material
consistent with usage for a minimum distance 10 feet from the hood and shall be
equipped with wash-down facilities.
N)Â Â Â Â Â Â Â The hood and duct system for cooking equipment used in
processes producing smoke or grease-laden vapors shall comply with NFPA 96,
Standard for Ventilation Control and Fire Protection of Commercial Cooking
Operations. That portion of the fire extinguishment system required for
protection of the duct system may be omitted when all cooking equipment is
served by listed grease extractors.
O)Â Â Â Â Â Â Â Other exhaust hoods in food preparation centers shall have an
adequate exhaust rate.
P)Â Â Â Â Â Â Â Â Clean-out openings shall be provided to allow proper cleaning
of the duct system serving kitchen and food preparation areas.
Q)Â Â Â Â Â Â Â The ventilation system for anesthesia storage rooms shall
conform to the requirements of NFPA 99, Standard for Health Care Facilities,
including the gravity option system.
R)Â Â Â Â Â Â Â Boiler rooms shall be provided with sufficient outdoor air to
maintain proper combustion rates for equipment.
S)Â Â Â Â Â Â Â Â Rooms containing heat-producing equipment, such as boiler
rooms, heater rooms, food preparation centers, laundries, and sterilizer rooms,
shall be ventilated.
T)Â Â Â Â Â Â Â Â For general pressure relationships and ventilation of certain
hospital areas, see Table F.