77 Ill. Adm. Code 250.2650
Finishes
Section 250
Section 250.2650Â Finishes
a)Â Â Â Â Â Â Â Â Cubicle and window curtains and draperies shall be
noncombustible or rendered flame retardant and shall pass both the large and
small scale tests of NFPA 701, Standard Methods of Fire Tests for Flame
Propagation of Textiles and Films.
b)Â Â Â Â Â Â Â Â Floors in areas and rooms in which flammable anesthetic agents
are stored or administered to patients shall comply with NFPA 99, Standard for
Health Care Facilities, "Inhalation Anesthetics". Conductive flooring
is not required in emergency treatment, operating, and delivery rooms provided
that a written resolution is signed by the hospital governing board stating
that no flammable anesthetic agents will be used in these areas, and provided
that appropriate notices are permanently and conspicuously affixed to the wall
in each such area and room.
c)Â Â Â Â Â Â Â Â Floor materials shall be easily cleanable and have wear
resistance appropriate for the location involved. Floors in areas used for
food preparation or food assembly shall be water-resistant and grease-proof.Â
Joints in tile and similar material in such areas shall be resistant to food
acids. Floors in toilets, baths, janitor's closets and similar areas shall be
water resistant. In all areas frequently subject to wet cleaning methods,
floor materials shall not be physically affected by germicidal and cleaning
solutions.
d)Â Â Â Â Â Â Â Â Wall bases in kitchens, operating and delivery rooms, soiled
workrooms, and other areas that are frequently subject to wet cleaning methods
shall be tightly sealed to the wall and floor and constructed without surface
voids that can harbor vermin.
e)Â Â Â Â Â Â Â Â All wall finishes shall be washable and, in the immediate area
of plumbing fixtures, shall be smooth and moisture resistant. Walls in surgery,
delivery, kitchens, and in other spaces subject to frequent cleaning shall be
of suitable materials.
f)Â Â Â Â Â Â Â Â Floor and wall penetrations by pipes, ducts, and conduits
shall be tightly sealed to minimize entry of vermin, smoke, and fire. Joints of
structural elements shall be similarly sealed.
g)Â Â Â Â Â Â Â Â Ceilings shall be cleanable, and those in sensitive areas such
as surgical, delivery, and nursery rooms shall be readily washable and without
crevices that can retain dirt particles. These sensitive areas, along with the
dietary and food preparation areas, shall have a finished ceiling covering all
overhead ductwork. Finished ceilings may be omitted in mechanical and
equipment spaces, shops, general storage areas, and similar spaces, unless
required for fire-resistive purposes.