77 Ill. Adm. Code 250.2640
Details
Section 250
Section 250.2640Â Details
All details and finishes shall
comply with the following:
a)Â Â Â Â Â Â Â Â Details
1)Â Â Â Â Â Â Â Â Compartmentation, exits, automatic extinguishing systems and
other details relating to fire prevention and fire protection shall comply with
requirements listed in the appropriate sections of NFPA 101, Life Safety Code,
, for existing hospitals (for exception, see subsection (a)(2) of this
Section).
2)Â Â Â Â Â Â Â Â Aisles, corridors, and interior ramps required for exit access
from patient sleeping areas shall have a minimum clear width of 7 feet; any
such aisles, corridors, and interior ramps located in other patient use areas
shall have a minimum clear width of 6 feet.
3)Â Â Â Â Â Â Â Â Doors to patient rooms shall not be lockable from inside the
room.
4)Â Â Â Â Â Â Â Â Doors on all openings between corridors and rooms or spaces
subject to occupancy, except elevator doors, shall be swing type. Openings to
showers, baths, patient toilets, and other small wet-type areas not subject to
fire hazard are exempt from this requirement. Sliding doors with a break-and-swing
feature are acceptable.
5)Â Â Â Â Â Â Â Â Glazing of existing doors, sidelights, borrowed lights, and
interior windows shall comply with the Safety Glazing Materials Act.
6)        Elevator shaft openings shall be class B 1½-hour-labeled fire
doors or shall meet the requirements of NFPA 101, Life Safety Code, for
vertical shaft enclosure.
7)Â Â Â Â Â Â Â Â Linen and refuse chutes shall meet or exceed the following
requirements:
A)Â Â Â Â Â Â Â Service openings to chutes shall be kept locked if located in
corridors or passageways. They may be located in a room of construction having
a fire-resistance of not less than one hour.
B)Â Â Â Â Â Â Â Service openings to chutes shall have approved self-closing
class B 1½-hour-labeled fire doors.
C)Â Â Â Â Â Â Â Chutes shall discharge directly into collection rooms separated
from incinerator, laundry, or other services. Separate collection rooms shall
be provided for trash and for linen. The enclosure construction for such rooms
shall have a fire resistance of not less than two hours, and the doors shall be
not less than class B 1½-hour-labeled fire doors. External discharge
containers need not be enclosed.
D)Â Â Â Â Â Â Â Gravity chutes shall be vented through the roof with provisions
for continuous ventilation as well as for fire and smoke ventilation. Fire and
smoke ventilating openings may be covered with single strength sheet glass.
E)Â Â Â Â Â Â Â See NFPA 82, Standard on Incinerators and Waste and Linen
Handling Systems and Equipment for other requirements.
8)Â Â Â Â Â Â Â Â Grab bars shall be provided at all patients' toilets, showers,
tubs, and sitz baths. The bars shall have 1½-inch clearance to walls and shall
be securely anchored.
9)Â Â Â Â Â Â Â Â Location and arrangement of hand-washing facilities shall
permit their proper use and operation. Clearance for blade-type operating
handles shall be provided where required.
10)Â Â Â Â Â Â Â Â Mirrors shall not be installed at hand-washing fixtures in
food preparation areas or in sensitive areas such as nurseries, clean and sterile
supplies, and scrub sinks.
11)Â Â Â Â Â Â Â Â Paper towel dispensers and waste receptacles or electric hand
dryers shall be provided at all hand-washing facilities except scrub sinks.
b)Â Â Â Â Â Â Â Â Elevators
All hospitals having patients' facilities (such as bedrooms,
dining rooms, or recreation areas) or critical services (such as operating,
delivery, diagnostic, or therapy) located on other than the main entrance floor
shall have electric or electrohydraulic elevators.
1)Â Â Â Â Â Â Â Â Number of elevators.
A)Â Â Â Â Â Â Â At least one hospital-type elevator shall be installed where
one to 59 patient beds are located on any floor other than the main entrance
floor.
B)Â Â Â Â Â Â Â At least two hospital-type elevators shall be installed where
60 to 200 patient beds are located on floors other than the main entrance
floor, or where the major inpatient services are located on a floor other than
those containing patient beds. (Elevator service may be reduced for those
floors that provide only partial inpatient services.)
C)Â Â Â Â Â Â Â At least three hospital-type elevators shall be installed where
201 to 350 patient beds are located on floors other than the main entrance
floor, or where the major inpatient services are located on a floor other than
those containing patient beds. (Elevator service may be reduced for those
floors that provide only partial inpatient services.)
D)Â Â Â Â Â Â Â For hospitals with more than 350 beds, the number of elevators
provided shall be based on the hospital's program narrative.
2)        Cars and platforms. Cars of hospital-type elevators shall
have dimensions that will accommodate a patient bed and attendants and shall be
at least 5 feet by 7 feet. The car door shall have a clear opening of not less
than 3 feet, 8 inches.
3)        Leveling. Elevators shall be equipped with an automatic
leveling device of the two-way automatic maintaining type with an accuracy of +½
inch.
4)Â Â Â Â Â Â Â Â Written certification of the latest inspection shall be posted
in the cab if available.
c)Â Â Â Â Â Â Â Â Provisions for Natural Disasters
General requirements. An emergency radio communication
system is desirable in each hospital. If installed, this system shall be
self-sufficient in time of emergency and shall also be linked with the
available community system and state emergency medical network system,
including connections with police, fire, and civil defense system.