77 Ill. Adm. Code 264.2850
Heating, Ventilating and Air-Conditioning Systems (HVAC)
Section 264.2850Â Heating, Ventilating and
Air-Conditioning Systems (HVAC)
a)Â Â Â Â Â Â Â Â General
1)Â Â Â Â Â Â Â Â Mechanical
System Design
A)Â Â Â Â Â Â Â Efficiency.
The mechanical system shall be designed for overall efficiency and appropriate
life-cycle cost.
i)Â Â Â Â Â Â Â Â Â Recognized
engineering procedures shall be followed for the most economical and effective
results.
ii)Â Â Â Â Â Â Â Â Client
care or safety shall not be sacrificed for conservation.
iii)Â Â Â Â Â Â Â If
possible, the birth center shall include provisions for recovery of waste
cooling and heating energy (e.g., ventilation, exhaust, water and steam
discharge, cooling towers, incinerators, etc.).
iv)Â Â Â Â Â Â Â Use
of recognized energy-saving mechanisms such as variable-air-volume (VAV)
systems, and use of natural ventilation shall be considered, site and climatic
conditions permitting.
v)Â Â Â Â Â Â Â Â Birth
center design considerations shall include site, building mass, orientation,
configuration, fenestration, and other features relative to passive and active
energy systems.
B)Â Â Â Â Â Â Â Air-handling
Systems
i)Â Â Â Â Â Â Â Â Â These
shall be designed with an economizer cycle, where appropriate to use outside
air. (Use of mechanically-circulated outside air does not reduce the need for
filtration.)
ii)Â Â Â Â Â Â Â Â VAV
Systems. The energy-saving potential of variable-air-volume systems is
recognized, and the standards in this Section are intended to maximize
appropriate use of those systems. Any system used for occupied areas must
include provisions to avoid air stagnation in interior spaces where thermostat
demands are met by temperatures of surrounding areas.
iii)Â Â Â Â Â Â Â Noncentral
air-handling systems (i.e., individual room units used for heating and cooling
purposes, such as fan-coil units, heat pump units, etc.) may be used as
recirculating units only. All outdoor air requirements shall be met by a
separate central air-handling system with proper filtration, as noted in
Section 2.1-8.2.1.2
of the AIA Guidelines.
C)Â Â Â Â Â Â Â System
Valves. Supply and return mains and risers for cooling, heating, and steam
systems shall be equipped with valves to isolate the various sections of each
system. Each piece of equipment shall have valves at the supply and return
ends.
D)Â Â Â Â Â Â Â Renovation.
If system modifications affect greater than 10 percent of the system capacity,
designers shall use pre-renovation water/air flow rate measurements to verify
that sufficient capacity is available and that renovations have not adversely
affected flow rates in non-renovated areas.
2)Â Â Â Â Â Â Â Â Ventilation
and Space Conditioning Requirements. All rooms and areas used for client care
shall have provisions for ventilation.
A)Â Â Â Â Â Â Â Ventilation
Rates. The ventilation systems shall be designed and balanced, as a minimum,
according to the requirements shown in Section 2.1-8.2.1.2 and the applicable
notes of the AIA Guidelines. The ventilation rates shown in Section 2.1-8.2.1.2
do not preclude the use of higher rates.
B)Â Â Â Â Â Â Â Temperature
and Humidity. Space temperature and relative humidity shall be as indicated in
Section 2.1-8.2.1.2
of the AIA Guidelines.
C)Â Â Â Â Â Â Â Air
Movement Direction. To maintain asepsis control, airflow supply and exhaust
shall generally be controlled to ensure movement of air from "clean"
to "less clean" areas, especially in critical areas.
D)Â Â Â Â Â Â Â Mechanical
Ventilation. Although natural ventilation for non-sensitive areas and client
rooms (via operable windows) shall be permitted, mechanical ventilation shall
be considered for all rooms and areas in the birth center.
3)Â Â Â Â Â Â Â Â Testing
and Documentation
A)Â Â Â Â Â Â Â Upon
completion of the equipment installation contract, the owner shall be furnished
with a complete set of manufacturers' operating, maintenance, and preventive
maintenance instructions, parts lists, and complete procurement information,
including equipment numbers and descriptions. Required information shall
include energy ratings as needed for future conservation calculations. This
information shall be always kept by and at the birth center.
B)Â Â Â Â Â Â Â Operating
staff persons shall also be provided with written instructions for proper
operation of systems and equipment.
b)Â Â Â Â Â Â Â Â Requirements
for Specific Locations
1)Â Â Â Â Â Â Â Â Birth
Rooms
A)Â Â Â Â Â Â Â Air Supply
i)Â Â Â Â Â Â Â Â Â Air
supply for birth rooms shall be from non-aspirating ceiling diffusers with a
face velocity in the range of 25 to 35 fpm (0.13 to 0.18 m/s), located at the
ceiling above the center of the work area. Return air shall be near the floor
level, at a minimum. Return air shall be permitted high on the walls, in
addition to the low returns.
ii)Â Â Â Â Â Â Â Â Each
birth room shall have at least two return-air inlets located as far from each
other as practical.
iii)Â Â Â Â Â Â Â Turbulence
and other factors of air movement shall be considered to minimize the fall of
particulates onto clean surfaces.
B)Â Â Â Â Â Â Â Temperature.
Temperature shall be individually controlled for each birth room.
C)Â Â Â Â Â Â Â Ventilation
Rates
i)Â Â Â Â Â Â Â Â Â Birth
room ventilation systems shall always operate, except during maintenance and
conditions requiring shutdown by the building's fire alarm system.
ii)Â Â Â Â Â Â Â Â During
unoccupied hours, birth room air change rates may be reduced, provided that the
positive room pressure is maintained as required in Section 2.1-8.2.1.2 of the
AIA Guidelines.
2)Â Â Â Â Â Â Â Â Fuel-fired
Equipment Rooms. Rooms with fuel-fired equipment shall be provided with
sufficient outdoor air to maintain equipment combustion rates and to limit
workstation temperatures.
3)Â Â Â Â Â Â Â Â Clean
workrooms or clean holding rooms and soiled workrooms or soiled holding rooms
shall comply with ventilation requirements per Section 2.1-8.2.1.2 of the AIA
Guidelines.
c)Â Â Â Â Â Â Â Â HVAC
Air Distribution
1)Â Â Â Â Â Â Â Â Return
Air Systems. For client care areas, return air must be by means of ducted
systems.
2)Â Â Â Â Â Â Â Â HVAC
Ductwork. See Section 1.6-2.2.2.1 of the AIA Guidelines. Exception: The use
of lined ductwork is not permitted to serve any client area in the birth
center.
3)Â Â Â Â Â Â Â Â Exhaust
Systems − General
A)Â Â Â Â Â Â Â To
enhance the efficiency of recovery devices required for energy conservation,
combined exhaust systems shall be permitted.
B)Â Â Â Â Â Â Â Local
exhaust systems shall be used whenever possible in place of dilution
ventilation to reduce exposure to hazardous gases, vapors, fumes, or mists.
C)Â Â Â Â Â Â Â Fans
serving exhaust systems shall be located at the discharge end and shall be
readily serviceable.
4)Â Â Â Â Â Â Â Â Air
Outlets and Inlets – Fresh Air Intakes
A)Â Â Â Â Â Â Â Fresh
air intakes shall be located at least 25 feet (7.62 meters) from exhaust
outlets of ventilating systems, combustion vents (including those serving
rooftop air handling equipment), medical-surgical vacuum systems, plumbing
vents, or areas that may collect vehicular exhaust or other noxious fumes.
(Prevailing winds and/or proximity to other structures may require greater
clearances.)
B)Â Â Â Â Â Â Â Plumbing
vents that terminate at a level above the top of the air intake may be located
as close as 10 feet (3.05 meters).
C)Â Â Â Â Â Â Â The
bottom of outdoor air intakes serving central systems shall be as high as
practical, but at least 6 feet (1.83 meters) above ground level, or, if
installed above the roof, 3 feet (91.44 centimeters) above roof level.
d)Â Â Â Â Â Â Â Â HVAC
Filters
1)Â Â Â Â Â Â Â Â Filter
Efficiencies
A)Â Â Â Â Â Â Â All
central ventilation or air conditioning systems shall be equipped with filters
with efficiencies equal to, or greater than, those specified Section
2.1-8.2.1.2
of the AIA Guidelines.
B)Â Â Â Â Â Â Â Noncentral
air-handling systems shall be equipped with permanent (cleanable) or
replaceable filters with a minimum efficiency of Minimum Efficiency Reporting
Value (MERV) 3.
C)Â Â Â Â Â Â Â Filter
efficiencies, tested in accordance with ASHRAE 52.2 (ASHRAE Handbook of
Fundamentals), shall be average.
2)Â Â Â Â Â Â Â Â Filter
Bed Location. Where two filter beds are required, filter bed no. 1 shall be
located upstream of the air conditioning equipment and filter bed no. 2 shall
be downstream of any fan or blowers.
3)Â Â Â Â Â Â Â Â Filter
Frames. Filter frames shall be durable and proportioned to provide an airtight
fit with the enclosing ductwork. All joints between filter segments and
enclosing ductwork shall have gaskets or seals to provide a positive seal
against air leakage.
4)Â Â Â Â Â Â Â Â Filter
Housing Blank-off Panels. Filter housing blank-off panels shall be permanently
attached to the frame and constructed of rigid materials and shall have sealing
surfaces equal to or greater than the filter media installed in the filter
frame.
5)Â Â Â Â Â Â Â Â Filter
Manometers. A manometer shall be installed across each filter bed having a
required efficiency of 75 percent or more, including hoods requiring HEPA
filters. Provisions shall be made to allow access to the manometer for field
testing.
e)Â Â Â Â Â Â Â Â Steam
and Hot Water Systems. See Section 2.1-8.2.1.2 of the AIA Guidelines.