77 Ill. Adm. Code 264.2900
Electrical Systems
Section 264.2900Â Electrical Systems
a)Â Â Â Â Â Â Â Â General
1)Â Â Â Â Â Â Â Â Applicable
Standards
A)Â Â Â Â Â Â Â All
electrical material and equipment, including conductors, controls, and
signaling devices, shall be installed in compliance with applicable sections of
NFPA 70 and NFPA 99.
B)Â Â Â Â Â Â Â All
electrical material and equipment shall be listed as complying with available
standards of listing agencies or other similar established standards when such
standards are required.
C)Â Â Â Â Â Â Â Field
labeling of equipment and materials shall be permitted only when provided by a
nationally recognized testing laboratory that has been certified by the
Occupational Safety and Health Administration (OSHA) for that referenced
standard.
2)Â Â Â Â Â Â Â Â Testing
and Documentation. The electrical installations, including alarm, nurse call,
and communication systems, shall be tested to demonstrate that equipment
installation and operation is appropriate and functional. A written record of
performance tests on special electrical systems and equipment shall show
compliance with applicable codes and standards.
b)Â Â Â Â Â Â Â Â Electrical Distribution
and Transmission
1)Â Â Â Â Â Â Â Â Switchboards
A)Â Â Â Â Â Â Â Location
i)Â Â Â Â Â Â Â Â Â Main
switchboards shall be in an area separate from plumbing and mechanical
equipment and shall be accessible to authorized persons only.
ii)Â Â Â Â Â Â Â Â Switchboards
shall be convenient for use, readily accessible for maintenance, and away from
traffic lanes.
iii)Â Â Â Â Â Â Â Switchboards
shall be in a dry, ventilated space free of corrosive or explosive fumes,
gases, or any flammable material.
B)Â Â Â Â Â Â Â Overload
Protective Devices. These shall operate properly in ambient room temperatures.
2)Â Â Â Â Â Â Â Â Panelboards
A)Â Â Â Â Â Â Â Panelboards
serving critical branch, equipment system, or normal system loads shall be
located on the same floor as the loads to be served.
B)Â Â Â Â Â Â Â Location
of panelboards serving life safety branch loads on the floor above or the floor
below the loads to be served shall be permitted.
C)Â Â Â Â Â Â Â New
panelboards shall not be in public access corridors.
3)Â Â Â Â Â Â Â Â Ground-fault
Circuit Interrupters
A)Â Â Â Â Â Â Â Ground-fault
circuit interrupters (GFCIs) shall comply with NFPA 70.
B)Â Â Â Â Â Â Â When
ground-fault circuit interrupters are used in critical areas, provisions shall
be made to ensure that other essential equipment is not affected by activation
of one interrupter.
c)Â Â Â Â Â Â Â Â Power Generating and Storing
Equipment
Emergency Electrical Service.Â
Emergency power shall be provided for in accordance with NFPA 99, NFPA 101, and
NFPA 110.
d)Â Â Â Â Â Â Â Â Lighting
1)Â Â Â Â Â Â Â Â General.
See Section 1.6-2.3.1.1 of the AIA Guidelines.
2)Â Â Â Â Â Â Â Â Lighting
for Specific Locations in the Birth Center
A)Â Â Â Â Â Â Â Birth
Rooms. Birth rooms shall have general lighting and night lighting.
i)Â Â Â Â Â Â Â Â Â A
reading light shall be provided for each client. Reading light controls shall
be accessible to the client without the client having to get out of bed.Â
Incandescent and halogen light sources that produce heat shall be avoided to
prevent burns to the client and/or bed linen. Unless specifically designed to
protect the space below, the light source shall be covered by a diffuser or
lens. Flexible light arms, if used, shall be mechanically controlled to prevent
the lamp from contacting the bed linen.
ii)Â Â Â Â Â Â Â Â At
least one night light fixture in each birth room shall be controlled at the
room entrance.
B)Â Â Â Â Â Â Â Corridors
shall have general illumination with provisions for reducing light levels at
night.
3)Â Â Â Â Â Â Â Â Emergency
Lighting. See Section 1.6-2.3.1.2 of the AIA Guidelines.
4)Â Â Â Â Â Â Â Â Exit
Signs. See Section 1.6-2.3.1.3 of the AIA Guidelines.
e)Â Â Â Â Â Â Â Â Receptacles
1)Â Â Â Â Â Â Â Â Receptacles
in Corridors. Duplex-grounded receptacles for general use shall be installed
approximately 50 feet (15.24 meters) apart in all corridors and within 25 feet
(7.62 meters) of corridor ends.
2)Â Â Â Â Â Â Â Â Birth
Rooms. Each birth room shall have duplex-grounded receptacles. One receptacle
shall be at each side of the head of each bed; one for television, if used; one
on every other wall; and one for each motorized bed.
3)Â Â Â Â Â Â Â Â Emergency
System Receptacles. Electrical receptacle cover plates or electrical
receptacles supplied from the emergency systems shall be distinctively colored
or marked for identification. If color is used for identification purposes, the
same color shall be used throughout the birth center.
f)Â Â Â Â Â Â Â Â Call Systems
Each birthing room shall be
equipped with a system of communicating to other parts of the birth center and
to an outside telephone line. Specific locations in the Birth Center such as
toilet and bathing area shall have a process by which a client can communicate
with the birth center in the event of an emergency.