77 Ill. Adm. Code 330.3930
Occupancy and Fire Areas
Section 330
Section 330.3930Â Occupancy
and Fire Areas
Every existing facility shall
meet the following requirements:
a)Â Â Â Â Â Â Â Â Buildings with "nonfire resistive" type construction
shall not house any residents above the second floor. The third and fourth
floors of facilities, including Residential Care (Half-Way) Homes that were in
operation in the City of Chicago and subject to the local licensing ordinance
for such homes in December 1968 may be approved for alert ambulatory residents
if the facility is protected by an approved automatic sprinkler system or
approved automatic fire detection and alarm system directly connected to the
nearest available fire department in addition to the other usual fire
protection measures. (A, B)
b)Â Â Â Â Â Â Â Â A basement shall not be counted as a floor unless the floor
above is more than eight feet, six inches above the ground level at any
adjacent point of the building. Service and entrance area ways encompassing
not more than 25 percent of the perimeter of the building may be disregarded.
c)Â Â Â Â Â Â Â Â Attic and roof spaces, when designed for occupancy or used for
storage, shall be considered as an additional story in a building.
d)Â Â Â Â Â Â Â Â Any facility which is especially susceptible to rapid spread
of fire by reason of combustible construction, unenclosed vertical openings, or
other inflammable conditions, shall be protected by an approved automatic fire
detection and alarm system with direct connection to the fire department or an
approved automatic sprinkler system with a flow alarm. (A)
e)Â Â Â Â Â Â Â Â All sheltered care facilities that are not of fire restrictive
or protected noncombustible type construction, shall be protected by an
approved automatic sprinkler system with flow alarm. (A)