77 Ill. Adm. Code 330.3950
Stairways, Vertical Openings, and Doorways
Section 330
Section 330.3950Â Stairways,
Vertical Openings, and Doorways
Every existing facility shall
meet the following requirements:
a)Â Â Â Â Â Â Â Â All stairways shall be enclosed and protected with smokestop
partitions and doors at each floor level. All doors that are a part of this
protection shall swing in the direction of the exit from the building, be
provided with view panels of clear wired glass, and have door closers. These
doors shall be closed at all times when not in use. (A, B)
b)Â Â Â Â Â Â Â Â All vertical openings or shafts (including elevators,
dumbwaiters, laundry chutes, and stairways) shall be completely lined with
metal or equivalent fire resistive material. Openings into shafts shall be
protected with self-closing fire resistive doors. A sprinkler head or
detection device is recommended in each shaft. (A, B)
c)Â Â Â Â Â Â Â Â All required exterior exit doors shall swing outward, be
equipped with panic hardware, and be free of any obstruction. No chain
locking, or holding device shall be permitted on any door equipped with panic
hardware other than the latching mechanism of the panic hardware itself. If
the doors have no latching mechanism, panic hardware may not be required. (A,
B)
d)Â Â Â Â Â Â Â Â Interior kitchen doors shall be covered with fire resistive
material on the kitchen side with a view panel of clear, wired glass. All such
doors shall swing into the kitchen and shall be kept closed at all times when not
in use unless otherwise approved by the Department. Such approval will be
granted only when such variance will not create a hazard to the health,
welfare, or safety of residents. (B)
e)Â Â Â Â Â Â Â Â All doors from the basement which lead into the interior of the
building shall be self-closing, be covered with fire resistive material on the
basement side, and have a view panel of clear wired glass. These doors shall
be closed at all times when not in use. (B)