77 Ill. Adm. Code 350.2730
Plumbing Systems
Section 350
Section 350.2730Â Plumbing
Systems
a)Â Â Â Â Â Â Â Â All plumbing systems shall be designed and installed in
accordance with the requirements of the Department's rules entitled
"Illinois Plumbing Code" except that the number of resident required
(77 Ill. Adm. Code 890) water closets, lavatories, bathtubs, showers, and other
fixtures shall be as required by these standards and the facility program. (B)
b)Â Â Â Â Â Â Â Â Plumbing Fixtures
1)Â Â Â Â Â Â Â Â Plumbing fixtures shall be of non-absorptive acid-resistant
materials.
2)Â Â Â Â Â Â Â Â The water supply spout for lavatories and sinks required for
filling pitchers, for nursing staff and food handlers' handwashing, shall be
mounted so that its discharge point is a minimum distance of five inches above
the rim of the fixture. (B)
3)Â Â Â Â Â Â Â Â Handwashing lavatories used by nursing staff and food handlers
shall be trimmed with valves which can be operated without the use of hands.
When blade handles are used for this purpose, the blade handles shall not
exceed four and one-half inches in length, except the handles on clinical sinks
shall not be less than six inches in length.
4)Â Â Â Â Â Â Â Â Clinical rim flush sinks shall have an integral trap in which
the upper portion of the trap seal provides a visible water surface.
5)Â Â Â Â Â Â Â Â The potwashing sink shall be a three compartment sink with one
compartment at least l4 inches deep.
6)Â Â Â Â Â Â Â Â Shower bases and tub bottoms shall be designed with nonslip
surfaces. (B)
c)Â Â Â Â Â Â Â Â Water Supply Systems
1)Â Â Â Â Â Â Â Â Water supply systems shall be designed to supply water at
sufficient pressure and volume to operate all fixtures and equipment during maximum
demand periods.
2)Â Â Â Â Â Â Â Â Each water service main, branch main, riser and branch to a
group of fixtures shall be valved. Stop valves shall be provided at each
fixture.
3)Â Â Â Â Â Â Â Â Flush valves installed on plumbing fixtures shall be of a
quiet operating type, equipped with silencers.
4)Â Â Â Â Â Â Â Â Hot water distribution systems shall be arranged to provide
hot water of at least 100 degrees Fahrenheit at each hot water outlet at all
times.
5)Â Â Â Â Â Â Â Â Hot water available to residents at shower, bathing and
handwashing facilities shall not exceed 110 degrees Fahrenheit (A, B)
6)Â Â Â Â Â Â Â Â Each hot water system serving resident areas shall include at
least one of the following equipment requirements to insure that the water
temperature does not exceed 110 degrees Fahrenheit:
A)Â Â Â Â Â Â Â A thermostatically controlled mixing valve, or
B)Â Â Â Â Â Â Â An aquastat which limits the water temperature in the water
heater to a maximum temperature of 110 degrees Fahrenheit and a solenoid
operated shut off valve activated by a sensing element in the water line which
shuts off the water and activates an alarm at the nurses station when the water
temperature exceeds 110 degrees Fahrenheit. (A, B)
d)Â Â Â Â Â Â Â Â Hot Water Heaters and Tanks
1)Â Â Â Â Â Â Â Â Capacity and Temperature Requirements
A)Â Â Â Â Â Â Â The hot water heating equipment shall have sufficient capacity
to supply water at the temperature and quantities in the following areas:
Resident
Service
Dietary
Laundry
gallons/hour/bed
6½
4
4½
Temperature (degrees
Fahrenheit)
110
140*
180
*180 degree Fahrenheit water is required at dishwasher and
pot and pan sink.
B)Â Â Â Â Â Â Â Water temperatures to be taken at the point of use or discharge
of the hot water or inlet to processing equipment.
2)Â Â Â Â Â Â Â Â Water storage tanks shall be fabricated of corrosion resistant
metal or lined with noncorrosive material.
e)Â Â Â Â Â Â Â Â Drainage Systems. Insofar as possible drainage piping shall
not be installed above the ceiling nor installed in an exposed location in food
preparation centers, food serving facilities, food storage areas, and other
critical areas. Special precautions shall be taken to protect these areas from
possible leakage or condensation from necessary overhead piping systems. (B)
f)Â Â Â Â Â Â Â Â Fire Extinguishing Systems
1)Â Â Â Â Â Â Â Â A complete automatic sprinkler system shall be installed
throughout all facilities regardless of construction type. (A, B)
2)Â Â Â Â Â Â Â Â All sprinkler and other fire extinguishing systems shall be
designed and installed in accordance with National Fire Protection Association
Standard 101l and referenced codes. (A, B)
3)Â Â Â Â Â Â Â Â All sprinkler systems shall be maintained in accordance with
National Fire Protection Association Standard 13A. (A, B)